3.4.2
DTT cooling unit assembly (installation)
2
1
Item
Designation
1
Unit contour
Make cut-outs for the DTT cooling unit
Requirements
- All general requirements are fulfilled, see
-
The cooling unit is de-energized.
Required tools and material
-
Saw
-
Use a switch cabinet cutter, if applicable
-
Protective covers
Procedure
Use a protective cover to protect the switch cabinet from chips.
Provide the switch cabinet with cut-outs and holes. For the prescribed dimensions, refer to the figure
the DTT cooling unit.
Deburr the cut edges.
Remove chips and assembly waste from the switch cabinet.
Cut-outs and holes have been made.
Operating Manual DTT 6401 Standard Controller (SC) 086100036 © Pfannenberg GmbH
Figure16 – DTT switch cabinet cut-out