GB
Assembly with quick-release frame
Unit preparation - unit cover removal
1
2
Figure 22 – Loosening the unit cover
Item
Designation
1
Right cover screws (2x)
3
Ground cable
Procedure
Unscrew the two screws on the right side of the unit (1) and the two screws on the left side of the unit (2).
Disconnect the ground cable (3); see the figure Loosening the unit cover.
Remove the four screws on the top side of the unit (4).
Carefully pull the unit cover (5) upwards; see the figure Unit cover removal.
The cover has been removed from the cooling unit.
Unit preparation – Bracket assembly
Figure 24 – Bracket assembly
Procedure
Make a hole in the insulation of the bracket opening (6) with a screwdriver. Make 2x on the right and 2x on the
left.
Mount the two brackets (7) with the four screws (7) and the four washers (accessory kit). The openings of the
brackets face forwards; see the figure Bracket assembly.
Install the cover and front panel in the reverse order.
Tighten the screws, connect the ground cables; see the figure – Cover installation.
Unit preparation is completed. The cooling unit is ready for installation with the quick-release frame.
Operating Manual DTT 6401 Standard Controller (SC) 086100036 © Pfannenberg GmbH
3
6
7
5
Figure 23 - Unit cover removal
Item
Designation
2
Left cover screws (2x)
4
Top cover screws (4x)
Figure 25 – Cover installation
4
Page 23 / 42