Switch cabinet assembly

Requirements
-
The M8 jack rings are screwed into the cooling unit, see
-
The cooling unit is secured correctly with lashing straps.
Required tools and material
-
Lashing straps, loading crane, if applicable
Procedure
 Raise the correctly secured cooling unit slowly and evenly; see figure
 Assembly the cooling in a level position.
 Position the cooling unit on the switch cabinet roof and align it with the cut-outs.
 Ensure that the condensate drain (1) is positioned at the lowest point.
 Install the condensate drain hose on a consistent decline and without kinks.
 The condensate drain hose length must not exceed 3 m.
 Check regularly during operation to ensure that the condensate water drains correctly.
 Position the cooling unit precisely in the cut-out.
 All six casement fasteners (2) on the inside of the switch cabinet; see the figure Cooling unit assembly - detail A.
 Screw in all six casement fasteners (2) on the inside of the switch cabinet over the rail to mount the cooling unit;
see the figure Cooling unit assembly - detail B.
The cooling unit is attached to the switch cabinet and ready for electrical connection, see .
Operating Manual DTT 6401 Standard Controller (SC) 086100036 © Pfannenberg GmbH
2
1
3
A
Figure 19 – Cooling unit assembly with casement fasteners
2
B
Mounting M8
.
jack rings
and DTT cooling unit
assembly.
Page 21 / 42

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Dtt serieDtt 6301

Tabla de contenido