11.2.3 Humidifier

Functions only with municipal water, and not with demineralised or softened water.
The humidifier with immersed electrodes has a card mounted inside the box to relay all information relating to the humidifier
directly to the CCU CONTROLLER. It adapts, within the allowable operating limits, to the physical and chemical properties of the
water used. Voltage is applied to the immersed electrodes, and an electrical current passes between them, heating the water to
boiling point. The water acts as an electrical resistor, ensuring continuity between the electrodes with a minimum of dissolved
salts.
(The water must have a conductivity of between 350 μS/cm and 125 μS/cm.)
Control voltage
Power input
in control circuit
High power circuit voltage
Power circuit
current (A)
Protection rating
Max. power
Factory power setting
Factory steam
flow rate setting
Steam flow rate
Water supply pressure
Max. water supply
flow rate
Conductivity of
supply water
Hydrogen ion activity (PH)
Drain water flow rate
ø
Water supply
ø
Drain
Hardness of TH supply water
Connection:
it is supplied with a flexible water supply tube at the back of the unit.
To drain it, carry out siphoning.
Warning: the water temperature can reach 100°C.
W40 to W115
24 V
Without 9 V A valve; with 35 V A valve
3-PH/400 V
8.7 A
16 A
6 kW
W40 to W100: 6 kW
W40 to W100, 8 kg/h: (100%)
W115 : 8 kg/h: (100%)
5 to 8 kg/h
1 to 8 bar
0.6 L/min
350 to 1250 μs/cm
7 to 8 ph
4 L/min
G ¾'' male
32 mm
100 to 400 mg/l Ca CO ³
EN - 15
EN
X0039,03.2015