salmson MULTI-HE 2G Instalación E Instrucciones De Puesta En Marcha página 29

Bombas horizontales multi-etapas en acero inoxidable
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

ENGLISH
Other defects, not detected by the converter, due to the pump.
CAUTION !
Before any operation, switch off the pump(s).
If the liquid is toxic, corrosive or dangerous for human being,
SALMSON or the qualified person in charge of the repairing
must be informed. In this case, clean the pump to ensure a
complete safety to the repairing man.
DEFECTS
8.1 THE PUMP
a)The pump does not run
IS RUNNING
BUT NO DELIVERY.
b)The internal parts are
c)Suction pipes are obstructed :
d)Air in suction pipes :
e)Suction pressure is too low,
8.2 THE PUMP
a)Loose on its foundation :
IS VIBRATING.
b)Particles obstructing the pump :
c)Difficult rotation of the pump :
8.3 NO SUFFICIENT
a)The motor speed is not
PRESSURE
FOR THE PUMP.
b)The motor is defective :
c)Bad filling of the pump :
d)The drain-priming plug is not
8.4 THE FLOW
a)The suction head (Ha) is not
IS IRREGULAR.
b)The suction pipe has a lower
c)The strainer and the suction pipe
d)In mode 2, the pressure sensor
8.5 IN MODE 2, THE PUMP
a)The non-return valve is not tight :
DON'T STOP
b)The non-return valve
IF THE FLOW IS ZERO.
c)The tank has low capacity due
CAUSES
quickly enough. :
obstructed by particles :
it causes generally
cavitation noise :
high enough :
fully tightened :
respected :
diameter than the one of the pump :
are partially obstructed :
is not adequate :
is not adequate :
to installation :
a) Check the adequate adjustment of the requirement (conformity to the required
points).
b) Let dismantle the pump and clean it.
c) Clean all the pipes.
d) Check tightness of the whole pipe up to the pump and make it tight.
e) Too high losses of load on suction or suction head is too high
(check the NPSH of the pump installed and of the installation).
a) Check and tighten completely the nuts of the stud bolts.
b) Have the pump dismantled and clean it.
c) Check the pump turns freely without abnormal sticking.
a) Check if the set value is correctly adjusted.
b) Replace it.
c) Open the venting device and vent until there are no more air bubbles.
d) Check it and screw it again.
a) Study again the installation conditions and the recommendations
described in this instruction.
b) The suction pipe must have at least the same diameter as the suction
pump port.
c) Remove and clean.
d) Put a sensor with conforming pressure scale and accuracy
(see chapter 4.4).
a) Clean it or change it.
b) Replace it by an adequate non-return valve.
c) Change it or add an other one on the installation.
29
REMEDIES

Publicidad

Tabla de contenido
loading

Tabla de contenido