ETHERNET
Only available in variant NMT(D) SMART C. (Detailed description available in NMTC module manual, which can
be find on: :»http://imp-pumps.com/documentation/«, or with scanning QR code on the cover page.)
The pump has a built in web server which allows you to access your pump directly via an existing Ethernet
connection. The default address for access to the pump is "nmtpump /" or 192.168.0.245/
The web server uses HTML pages to set/view:
Regulation mode settings
•
Regulation parameters (power, RPM, head, flow)
•
•
Relay settings
External control inputs settings
•
Current and previews error
•
•
Pump statistics (power consumption, run time and other)
MODBUS
Only available in variant NMT(D) SMART C. (Detailed description available in NMTC module manual, which can
be find on: :»http://imp-pumps.com/documentation/«, or with scanning QR code on the cover page.)
Pump has built in Modbus client, through which we can access pump information using the RS 485 standard or
ETHERNET (TCP/IP).
Modbus allows us to set and view:
•
Regulation mode settings,
•
Regulation parameters (power, RPM, head, flow),
Relay settings,
•
•
External control inputs settings,
•
Current and previews error,
Pump statistics (power consumption, run time and other).
•
RESETTING PUMP TO FACTORY SETTINGS
For resetting the pump to factory settings all three buttons must be held for 5 seconds. This way the pump will
set itself to automatic mode, delete previous height and power settings and unlock setting pump operation (if
locked).
Resetting of communications module needs following steps:
1. Disconnecting power from pump,
2. Set the 10-step switch to number 9
3. Turning the pump on and off again,
4. Setting the 10-step switch to number 1,
5. Turning the pump on.
Communications module should now be set to factory settings.