Identify the Load Type for Each Zone
In a GRAFIK 4000 Series system, lighting load types are set using the circuit selector in the panel. For other load
types (AC motors, Sivoia QED shades, and projection screens), the load type must be specified at the control unit. For
all loads, setting the load type at the control unit changes the LED display for that load type (see below).
Set the load type for each zone
3
ZONE 5
ZONE 6
FADE
Zone LEDs
To set this load type:
Lighting Loads
Dimmable Loads
Non-Dim (last on, first off)
Non-Dim (first on, first off)
Motorized Shades
AC Shades
Blinking LED
Sivoia QED Shades
Blinking
LED
R
TEMPORARY
2
ZONES
M S
LS
Check for
MASTER
1
Enter (exit)
setup mode
Select this
LED display
To identify the load type for each zone:
1. Enter setup mode. Press and hold the SCENE 1 and
OFF buttons for about three seconds, until the scene
LEDs cycle.
2. Check for LS in FADE window. LS is the first code to
display when you enter setup mode. In LS mode, ZONE
LEDs turn on from top to bottom.
3. Set the load type for each zone. Press the ZONE 5
4
,
or 6 button until the ZONE LEDs match the load type
connected to each zone. Refer to the following table for
each load type and its corresponding LEDs.
4. Exit setup mode. Press and hold the SCENE 1 and OFF
buttons for about three seconds, until scene LEDs stop
cycling.
In the sample 6-zone control unit shown here, Zone 5 is
set for a dimmable load, and Zone 6 is set for non-dim
(first on, first off).
Important Notes
U se for any dimmable load. NOTE: This is the factory preset
load type for each zone.
U se non-dim for any lights to be switched ON and OFF only—
not dimmed when fading between scenes. This load will be the
last to switch on and the first to switch off.
U se non-dim for any lights to be switched ON and OFF only—
not dimmed when fading between scenes. This load will be the
first to switch on and the first to switch off.
A C shades zones are factory set to unaffected in each scene.
To program shade positions for a scene, refer to page 18.
GRAFIK Eye 4000 control units must be addressed to control
shades. To assign addresses, refer to page 16.
S ivoia QED shade zones are factory set to unaffected in each
scene. To program shade positions for a scene, refer to page
18. GRAFIK Eye 4000 control units must be addressed to
control shades. To assign addresses, refer to page 16.
GRAFIK Eye
4000 Series Control Unit Installer's Guide 17
®