Parameter list
Display
Description
name
ICM OD (Opening
-
Degree)
¡01
Main Switch
Mode
¡02
Analog Input signal
¡03
Speed at ON/OFF and
¡04
Modulating Mode
¡05
Automatic calibration
Analog Output signal
¡06
Fail safe
¡07
¡09
Digital Input function
¡10
Password
Old Alarms
¡11
¡12
OD at powercut
ICM configuration
¡26
Service
Display
Description
name
OD %
¡50
AI [mA]
¡51
AI [V]
¡52
AO [mA]
¡53
¡54
DI
¡55
DO Close
¡56
DO Open
¡57
DO Alarm
¡58
MAS mP SW ver.
¡59
SLA mP SW ver.
Reset to factory setting:
1. Remove the power supply.
2. Activate down arrow and up arrow push buttons
at the same time.
3. Connect the power supply.
4. Release down arrow and up arrow push buttons.
5. When the display on ICAD (fig. 2) is alternating
between showing: CA and A1 the factory
resetting is complete.
© Danfoss A/S (AC-AKC/ frz), 10-2007
Factory
Min.
Max.
setting
0
100
-
1
2
1
1
2
1
1
4
2
1
100
100
0
1
0
0
2
2
1
4
1
1
2
1
0
199
0
A1
A99
-
0
100
50
0
6
0
Factory
Min.
Max.
setting
0
100
-
0
20
-
0
10
-
0
20
-
0
1
-
0
1
-
0
1
-
0
1
-
0
100
-
0
100
-
DKRCI.PI.HV0.A1.53 / 520H0546
Unit
Comments
ICM valve Opening Degree is displayed during normal operation.
%
Running display value (see ¡01, ¡05).
Internal main switch
1: Normal operation
-
2: Manual operation. Valve Opening Degree will be flashing. With the down arrow
and the up arrow push buttons the OD can be entered manually.
Operation mode
1: Modulating – ICM positioning according to Analog Input (see ¡03)
-
2: ON/OFF - operating the ICM valve like an ON/OFF solenoid valve controlled via
Digital Input. See also ¡09.
Type of Analog Input signal from external controller
1: 0 - 20 mA
-
2: 4 - 20 mA
3: 0 - 10 V
4: 2 - 10 V
Speed can be decreased. Max. speed is 100 %
Not active when ¡01 = 2
If ¡02 = 2 the display will indicate speed in display. Low, Med and High also
%
means ON/OFF operation.
If ¡04 < = 33,
Low is displayed
33 < If ¡04 < = 66, Med is displayed
If ¡04 > = 67
High is displayed
Not active before ¡26 has been operated.
Always auto reset to 0.
-
CA" will flash in the display during calibration, if Enter push button has been
activated for two seconds.
Type of A0 signal for ICM valve position
0: No signal
-
1: 0 - 20 mA
2: 4 - 20 mA
Define condition at power cut when fail safe is installed.
1: Close valve
-
2: Open valve
3: Maintain valve position
4: Go to OD given by ¡12
Define function when DI is ON (short circuited DI terminals) when ¡02 = 2
1: Open ICM valve (DI = OFF = > Close ICM valve)
2: Close ICM valve (DI = OFF = > Open ICM valve)
Enter number to access password protected parameters: ¡26
-
Password = 11
Old alarms will be listed with the latest shown first. Alarm list can be reset by
-
means of activating down arrow and up arrow at the same time for 2 seconds.
Only active if ¡07 = 4
-
If fail safe supply is connected and powercut occurs ICM will go to entered OD.
NB: Password protected. Password = 11
At first start up A1 will flash in display. Enter valve type
0: No valve selected. Alarm A1 will become active.
1: ICM20 with ICAD 600
2: ICM25 with ICAD 600
3: ICM32 with ICAD 600
4: ICM40 with ICAD 900
5: ICM50 with ICAD 900
6: ICM65 with ICAD 900
Unit
Comments
%
ICM valve Opening Degree
mA
Analog Input signal
V
Analog Input signal
mA
Analog Output signal
-
Digital Input signal
-
Digital Output Closed status. ON when OD < 3 %
-
Digital Output Open status. ON when OD > 97 %
-
Digital Output alarm status. ON when an alarm is detected
-
Software version for MASTER Microprocessor
-
Software version for SLAVE Microprocessor