Nomenclature Of Weg Analog Voltage Regulators; Block Diagram - WEG WRGA-02 Manual De Instalación, Operación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. NOMENCLATURE OF WEG ANALOG VOLTAGE REGULATORS

WRGA – 02 /D AM/115

6. BLOCK DIAGRAM

Reference
+
+ - +
Operation is based in the comparison of the RMS sensing voltage with the reference voltage, adjusted by the sum of the voltage
adjustment trimpots and the external potentiometer. The error is processed by the sensing grid, and this value determines the
firing angle of the thyristor, controlling in this way the output voltage of the generator.
Generation starts through the generator residual voltage. After the voltage has reached approximately 10% of the rated value,
the regulator controls the voltage of the generator causing the voltage to increase in approximately 1 second, until it reaches
rated voltage. From this moment on, the control grid will maintain constant output voltage of the generator within the adjusted
value.
Rated power supply voltage
M = Single-phase
T = Three-phase
Sensing voltage Class
: A – 160-300V / 320-600V (selected by jumper)
/D- Identifies regulator for generator with PMG
Automatic voltage increase
PI
U/F
Sensing
DROOP
Figure 6.1 - Voltage regulator block diagram.
Power stage
Excitation field
Automatic Voltage Regulator – GRT7-TH4-R2
www.weg.net
Generator output
G
| 13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wrga-02/d

Tabla de contenido