16.
CONNECTION DIAGRAM WRGA-02/D
16.1 CONNECTIONS IN A GENERATOR WITH PMG AND THREE-PHASE SENSING
VOLTAGE
F +
Configuration for 160V to 300V
jumper on pins 1-2
JR
JS
JT
JCR
Figure 16.1 - WRGA-02/D connection diagram using PMG and three-phase sensing voltage.
1
Item not supplied by WEG;
2
For connection with single phase PMG, do not connect in AX3;
3
JR, JS and JT jumpers – Sensing voltage selector (pins 1-2 = 160 to 300Vac, pins 2-3 = 320 to 600Vac);
ATTENTION
1. Before connecting the regulator to the generator, verify in the installation manual, the rated sensing
voltage;
2. The sensing voltage can be different than the generator phase voltage. Note the point where the
sensing voltage is taken from (middle of the phase or complete phase).
3. If the sensing voltage is not equal to the output voltage of the generator, do not make the
connections without consulting the service department.
Generator
Switch On/Off
2
PMG
5
AX1
AX2
F+
F-
F -
Exciter field
3
Configuration for three-phase sensing
voltage jumper on pins 1-2
N
R
S
T
AX3
WRGA-02/D
4
.
Automatic Voltage Regulator – GRT7-TH4-R2
www.weg.net
N
R
S
T
Potentiometer for voltage external
adjustment
1
(5K/3W)
Configuration for 320V to 600V
jumper on pins 2-3
JR
3
JS
JT
JCR
| 25