BAW M12MI-BLC35C-S04G and BAW M12MH-BLC70G-S04G
Inductive Linear Position Sensor
6
IO-Link interface
6.1
Basic knowledge about IO-Link
General
IO-Link integrates conventional and intelligent sensors and
actuators in automation systems and is intended as a
communication standard within classic field buses. Field-
bus-independent transfer uses communication systems
that are already available (field buses or Ethernet-based
systems).
IO-Link devices, such as sensors and actuators, are
connected to the controlling system using a point-to-point
connection via a gateway, the IO-Link master. The IO-Link
devices are connected using commercially available
unshielded standard sensor cables.
Communication is based on a standard UART protocol
with a 24-V pulse modulation in half-duplex operation. This
allows classic three-conductor physics.
Protocol
With IO-Link communication, permanently defined frames
are cyclically exchanged between the IO-Link master and
the IO-Link device. In this protocol, both process and
required data, such as parameters or diagnostic data, is
transferred. The size and the type of the frame and the
cycle time used result from the combination of master and
device features (see Device specification on page 10).
Cycle time
The cycle time used (master cycle time) results from the
minimum possible cycle time of the IO-Link device
(min cycle time) and the minimum possible cycle time of
the IO-Link master. When selecting the IO-Link master,
please note that the larger value determines the cycle time
used.
Protocol version 1.0 / 1.1
In protocol version 1.0, process data larger than 2 bytes
was transferred spread over multiple cycles.
From protocol version 1.1, all available process data is
transferred in one frame. Thus, the cycle time (master cycle
time) is identical to the process data cycle.
The BAW M12M_-BLC_ _ _-... sensor is
optimized for protocol version 1.1 and cycle
time. Operating the IO-Link device on an IO-Link
master with protocol version 1.0 results in
longer transfer times (process data cycle ~
amount of process data x master cycle time).
www.balluff.com
Parameter management
A parameter manager that enables device parameters
to be saved on the IO-Link master is defined in protocol
version 1.1. When exchanging an IO-Link device, the
parameter data of the previously installed IO-Link device
can be taken over. The operation of this parameter
manager is dependent on the IO-Link master and is
explained in the corresponding description.
All parameters saved in the IO-Link master for
parameter management are indicated
correspondingly in Tab. 6-3 on page 10.
Device functions and master gateway
The functions of the sensor BAW M12M_-BLC_ _ _-... are
described in detail in sections 6.3 to 6.13. How process
and parameter data is implemented via the master
gateway can be found in the instructions for the IO-Link
master.
english
9