gefran 2300 Manual De Uso página 24

Visualizador / interceptador veloz
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 66
Sr.P
Serial interface protocol
0 CENCAL GEFRAN
1 MODBUS
bA.u Baudrate
bAu
Baudrate
0
1200
1
2400
2
4800
3
9600
4
19200
(CL = Current Loop)
PA.r
Parity
0 No parity
1 Odd parity
2 Even parity
butt.1
PEAK key function
0 no function (key not active)
1 activate "peak +" (maximum) (*)
2 activate "peak -" (minimum)
3 activate "peak-peak" (max. peak - min. peak)
butt.2
CAL/RST key function
0 no function (key not active)
1 reset trip memory
2 reset peak memory
3 reset trip memory + reset peak memory
4 tare reset
5 tare reset + setpoint memory reset
6 tare reset + peak memory reset
7 tare reset + setpoint memory reset + peak memory reset
8 calibration check
9 remote setpoint 1 on/off (•)
10 remote setpoint 2 on/off (•)
11 remote setpoint 1+2 on/off (•)
12 display HOLD function (the display remains "frozen" as long as the key is pressed); the process variable continues
to be sampled and the setpoints function normally
13 HOLD function for sampled input value (the sampled input value and the setpoints remain "frozen" as long as the
key is pressed)
butt.3
" * " key function
0 no function (key not active)
1 reset trip memory
2 reset peak memory
3 reset trip memory + reset peak memory
4 tare reset
5 tare reset + setpoint memory reset
6 tare reset + peak memory reset
7 tare reset + setpoint memory reset + peak memory reset
8 calibration check
9 remote setpoint 1 on/off (•)
10 remote setpoint 2 on/off (•)
11 remote setpoint 1+2 on/off (•)
12 display HOLD function (the display remains "frozen" as long as the key is pressed); the process variable continues
to be sampled and the setpoints function normally
13 HOLD function for sampled input value (the sampled input value and the setpoints remain "frozen" as long as the
key is pressed)
14 NET/GROSS selection function. The GROSS display is indicated by the flashing decimal point of the units. The set
points always refer to the NET value. In case of PV configuration as sum of inputs, the key switches between main
input and sum of inputs. The main variable is indicated by the flashing decimal point of the units. In this case, the
setpoints refer to the sum of inputs.
(•) Remote setpoint enabled; REM LED on, tYPr1 and/or tYPr2 must also be enabled in CFG3.
8 • CONFIGURATIONS
Interface
CL/485
485
485
485
485
24

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido