Technical Data; Accessory - Roca TECNO 190-L Instrucciones De Instalación, Funcionamiento Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

TECHNICAL DATA

MODEL
OUTPUT
(1)
DELIVERY
(1)
FUEL
- net calorific value
- density
- viscosity at 20 °C
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
Running current
Start-up current
IGNITION TRANSFORMER
CONTROL BOX
PUMP J7C
delivery (at 12 bar)
pressure range
fuel temperature
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
IN CONFORMITY WITH EEC DIRECTIVES
NOISE LEVELS
(2)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
(2)
ACCESSORIE (optional):
STATUS (see page 15): code 3010322
2nd stage
kW
Mcal/h
kg/h
1st stage
kW
Mcal/h
kg/h
LIGHT OIL
kWh/kg
11.8
Mcal/kg
10.2 (10.200 kcal/kg)
0.82 - 0.85
3
kg/dm
max 6 (1.5 °E - 6 cSt)
2
mm
/s
• Intermittent (min. 1 stop in 24 hours).
• Two-stage (high and low flame) and single-stage (all - nothing)
number 2
Boilers: water, steam, diathermic oil
°C
0 - 40
°C max 60
V
230 - 400 with neutral +/-10%
Hz
50 - three-phase ~
rpm
W
V
A
A
V1 - V2
I1 - I2
kg/h
bar
° C max
W max
IP 44
89/336 - 73/23 - 89/392
dBA
TECNO 190L
1423 - 2443
1224 - 2100
120 - 206
759 - 1423
653 - 1224
64 - 120
2800
4500
220/240 - 380/415
15.8 - 9.1
126 - 72.8
230 V - 2 x 5 kV
1,9 A - 35 mA
RMO88.53A2
230
10 - 21
90
5870
83.9
2
GB