INSTALLATION INSTRUCTIONS FOR B400 SERIES PLUG IN DETECTOR BASES FOR USE
WITH SERIES 100, 300 AND 400 DETECTORS AND VARIANTS
Before installing bases, please thoroughly read the System Sensor's "Guide to Conventional Fire Systems", which provides information on
detector spacing, placement, zoning, wiring, and applications. Copies of this manual are available at no charge from System Sensor.
GENERAL DESCRIPTION
B400 series plug in detector bases are designed for use with System Sensor Series 100, 300 and 400 smoke and heat detectors and their variants.
Several base options are available permitting System Sensor heads to be used with a variety of 2-wire fire systems. The panel manufacturer
should be consulted to ensure that the correct base option is selected.
BASE OPTIONS
Base Name
Diameter
(mm)
B401
102
B401R
102
B401R1000
102
B401SD
102
B401RSD
102
B401DG
102
B401DGR
102
B401DGR1000
102
B401DGSD
102
SPECIFICATIONS
Operating Voltage:
Nominal 12 / 24VDC
Current:
See detector specifications.
Operating temperature range:
See detector specifications.
Operating humidity range:
See detector specifications.
INSTALLATION
Mounting
The detector base should be mounted using pan head screws, with a maximum thread diameter of 4mm, and maximum head diameter of 8mm.
If required, suitable junction boxes may be used. Mounting centres are shown in figure 1.
If Series 300 (or variant) single indicator detectors are to be used, the position of the detector indicator LED when installed will be in line with
terminal 4 on the base.
Wiring
All wiring must be installed in compliance with applicable local codes and standards, and the authority having jurisdiction.
The bases should be wired in accordance with figure 2b for bases fitted with resistors, and figure 2a for all other bases.
The base terminals are designed to accept cables between 0.75mm
for acceptable cable resistance and capacitance.
Note: Do not loop the wire under the terminals - to ensure supervision of contacts, the wire run must be broken.
To permit continuity testing of the wiring circuit prior to installation of the detector heads, the bases contains a shorting spring, which acts to
connect terminals 2 (negative in) and 3 (negative out) see figure 1. To activate, gently push the spring toward the centre of the detector until it
clips into place. The short will automatically disengage when the detector is installed.
Tamper Resist Feature
The detector base also includes a feature, which when activated prevents the removal of the detector without the use of a tool.
To activate this feature, break off the tab on the detector base prior to installing the detector (See figure 3a). To remove a detector once the tamper
resist feature has been activated, place a small bladed screwdriver into the small hole on the side of the base, push the lever away from the
detector and rotate the detector anti-clockwise (see figure 3b).
Note:
Do not activate the tamper resist feature if a removal tool is to be used - this feature is not reversible.
REMOTE ANNUNCIATOR UNITS
The model RA400Z Remote Annunciator LED is available as an optional accessory. This unit has a rectangular plate that fits US single-gang light
switch boxes.
If a different type of remote annunciator is used, it should be rated for 5mA at 3.0V
D450-40-00
Height
Weight
Resistor
Schottky
(mm)
(g)
(Ω)
Diode
20
53
-
-
20
55
470
-
20
55
1000
-
20
56
-
Yes
20
57
470
Yes
25.9
57
-
-
25.9
59
470
-
25.9
59
1000
-
25.9
60
-
Yes
2
and 2.5mm
2
, however reference should be made to the panel specifications
Figure 1: Terminal Layout
RESISTOR (RESISTOR BASES ONLY)
NOTE TERMINAL 5 IS NOT FITTED TO
NON-RESISTOR BASES.
Figure 2a: Non-Resistor Base Wiring
-
FROM CONTROL
PANEL OR
PREVIOUS
DEVICE
2
3
1
5
4
+
Figure 3a: Activation of Tamper Resist Feature
BREAK TAB AT DOTTED
PLASTIC LEVER
LINE BY TWISTING
TOWARD CENTRE OF BASE
Smoke detectors will only work when connected to a functioning, compatible control panel.
Smoke detectors have sensing limitations. They will not sense fires where smoke does not reach the sensor, and different types of
detector will respond differently to various smoke types.
Smoke detectors cannot last forever, and we recommended replacement after 10 years.
1
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
SCHOTTKY DIODE (FITTED TO DIODE BASES ONLY)
SHORTING SPRING - PERMITS TESTING OF
CIRCUIT PRIOR TO INSTALLATION OF
DETECTORS.
DISENGAGES AUTOMATICALLY
2
3
ON INSTALLATION OF DETECTOR.
1
4
POSITION OF INDICATOR WHEN
SINGLE LED DETECTOR IS FITTED
5
MOUNTING HOLE CENTRES.
NOTE - DASHED MOUNTING HOLES ARE
ALTERNATIVES AVAILABLE ON STANDARD
HEIGHT BASES ONLY - CENTRES 50MM
Figure 2b: Resistor Base Wiring
-
-
FROM
TO NEXT
CONTROL
DETECTOR
PANEL OR
OR END OF
PREVIOUS
2
LINE DEVICE
DEVICE
1
5
4
+
+
Figure 3b: Removing Detector Head from Base
USE SMALL BLADED SCREWDRIVER
TO PUSH THE PLASTIC LEVER IN THE
DIRECTION OF THE ARROW
WARNING
LIMITATIONS OF FIRE DETECTORS
-
TO NEXT
DETECTOR
OR END OF
LINE
DEVICE
3
+