Toshiba Carrier MMU-AP0074HPUL Manual De Instalación página 11

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation of ceiling opening and
hanging bolt
Hanging bolt
Level vial
Hanging bracket
• Attach a nut (M10 or W3/8: not supplied) and the
Ø1.33" (34 mm) washer (supplied) to each hanging
bolt.
• Insert a washer on both sides of the T groove of the
hanging bracket of the indoor unit, and hang the
indoor unit.
• Check that the four sides of the indoor unit are level
using a level vial (levelness: 0.20" (5 mm) or less).
• Detach the installation gauge (accessory) from the
installation pattern.
• Using the installation gauge, check and adjust the
positional relation between the indoor unit and the
ceiling opening (1) (0.4" to 1.4" (10 to 35 mm)
: 4 sides) and the hanging-up height (2)
(0.47"
+0.2"
(12
+5
mm): 4 corners).
0
0
(How to use the installation gauge is printed on the
gauge.)
* Procure hanging bolts
and nuts locally.
Hanging bolt
(M10 or W3/8)
Nut (M10 or W3/8)
Washer (Accessory)
To prevent the bolt
from falling off (for
Eccentric washer
safety), be sure to set
(Accessory)
it just under the
hanging bracket as
* Install with the marking
shown in the figure.
"UP" facing up.
Nut (M10 or W3/8)
19-EN
1115350150_EN-FR-ES.indb 10
1115350150_EN-FR-ES.indb 10
Level vial (levelness: 0.2" (5 mm) or less)
Hanging bolt
Indoor unit
Hanging
bracket
(1) 0.4" to 1.4"
(10 to 35 mm)
Ceiling
board
Installation gauge
Indoor unit
(2) 0.47"
+0.2"
0
(12
+5
mm)
Ceiling board
Installation
0
(1) 0.4" to 1.4"
gauge
(10 to 35 mm)
REQUIREMENT
Before installation of the indoor unit, be sure to remove
the tape for transportation between the fan and the bell
mouth. Running the unit without removing the tape may
damage the fan motor.
Be sure to remove the tape for
transportation between the fan and the
bell mouth.
■ Installation of plate conduit
Gr02 (Option in accessory)
Super Modular Multi System u
series (SMMS-u)
REQUIREMENT
For support electric wiring Super Modular Multi
System u series (SMMS-u)
1. Remove screw A for the fixation of the electrical
control box cover and loosened screw B.
Slide the cover inside so that the hook part can be
removed (The electrical control box cover remain
being hooked on the hinge.)
2. Remove the wiring cover mounting screws
(1 locations), and a wiring cover is removed.
Screws B
Screws A
Hinge
Screws
Cover of the electrical
Wiring cover
control box
3. Remove screw for the fixation of the wire box.
Screws
– 10 –
4. Remove screw 4 locations for the fixation cover pipe
and a cover pipe removed.
Screws
5. Remove plate conduit Gr01 and insert a plate
conduit Gr02 from accessory on the pipe cover and
then screw it with original screw.
Hook section
Plate conduit Gr01
Plate conduit Gr02
Screws