Installation and Maintenance Instructions
Table 2 SPL and Current Data: DC Model 55/56 Horn Tone
LEVEL
High
Med
Low
NOTICE: Apply wires only to the positions designated in Table 2. Other
variations could cause damage to the eHorn.
Table 3 SPL and Current Data: AC Model 52 Horn Tone
LEVEL
High
Med
Low
NOTICE: Apply wires only to the positions designated in Table 3. Other
variations could cause damage to the eHorn.
Table 4 SPL and Current Data: AC Model 55/56 Horn Tone
LEVEL
High
Med
Low
NOTICE: Apply wires only to the positions designated in Table 4. Other
variations could cause damage to the eHorn.
Mounting the eHorn
The eHorn can be mounted on any relatively flat surface with or
without the supplied mounting brackets The mounting surface
must be capable of supporting the weight of the eHorn. Four
installer‑supplied 1/4 in screws are required. Use screws that are
suitable for the mounting surface.
8
55/56 Horn Tone (330.0 Hz Steady)
TAPS
WIRE 1
WIRE 2
P1
P5
P1
P3
P2
P3
52 Horn Tone (315.6 Hz Steady)
TAPS
WIRE 1
WIRE 2
P2
P4
P1
P3
P2
P3
55/56 Horn Tone (330.0 Hz Steady)
TAPS
WIRE 1
WIRE 2
P3
P5
P1
P3
P2
P3
Model eHorn
SPL
(dBA @ 10 ft)
117
106
96
SPL
(dBA @ 10 ft)
114
111
101
SPL
(dBA @ 10 ft)
116
107
98
DC Current (A)
24 Vdc
3.3
0.5
0.24
AC Current (A)
120 Vac
240 Vac
0.78
0.40
0.35
0.16
0.15
0.03
AC Current (A)
120 Vac
240 Vac
0.76
0.41
0.16
0.08
0.10
0.06