2.7
Connection with a HotSwap MBP (Maintenance Bypass) Module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads
(HotSwap function).
Evolution 2500 / 3000
HotSwap MBP
HotSwap MBP module operation
UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2. Set switch (53) to Normal position.
3. Start the UPS by pressing the ON/OFF button (24) on the UPS control panel.
The load is supplied by the UPS.
LED (51) «UPS ON - OK to switch» on the HotSwap MBP module goes ON.
HotSwap MBP module test
1. Set switch (53) to Bypass position and check that the load is still supplied.
2. Set switch (53) back to Normal position.
1. Connect the input socket (56) on the HotSwap MBP
module to the AC-power source.
2. Connect the UPS input socket (10) to the «UPS
Input» (55) of the HotSwap MBP module.
This cord and the receptacle are marked blue.
3. Connect the UPS outlet (7) to the «UPS Output» (54)
of the HotSwap MBP module.
This cord and the outlet are marked red.
4. Connect the equipment to the outlets (49) on the
HotSwap MBP module.
54
55
These outlets differ, depending on the version of the
HotSwap MBP module.
Caution: Do not use UPS outlets (8) and (9) to
supply equipment because use of switch (53) on
the HotSwap MBP module would cut supply to the
equipment.
The HotSwap MBP module has a rotary switch (53)
with two positions:
Normal the load is supplied by the UPS, LED (51)
Bypass the load is supplied directly by the
2. Installation
is on.
AC-power source. LED (52) is on.
86-81710-00EN A03 - Page 15