Mounting the new battery module
Carry out the above instructions in reverse order.
◗
To ensure safety and high performance, use only batteries supplied by EATON Powerware
◗
Take care to firmly press together the two parts of the connector during remounting.
5.3 Maintenance on a UPS equipped with the HotSwap MBP module
HotSwap MBP
5.4 Training centre
For further information, please visit our website: www.powerware.com
7
49
50
51 52
The HotSwap MBP module makes it
8
possible to service or even replace the UPS
without affecting the connected loads
(HotSwap function).
Maintenance
1 - Set switch (53) to Bypass position. The red
LED on the HotSwap MBP module goes ON,
indicating that the load is supplied directly
with AC input source power.
9
10
2 - Stop the UPS by pressing the ON/OFF
button (24) on the UPS control panel. LED
44
(51) "UPS ON - OK to switch" goes OFF, the
UPS can now be disconnected and replaced.
Return to normal operation
1 - Check that the UPS is correctly connected
to the HotSwap MBP module.
2 - Start the UPS by pressing the ON/OFF
button (24) on the UPS control panel. LED
(51) "UPS ON - OK to switch" on the
HotSwap MBP module goes ON (otherwise,
53
54
55
56
there is a connection error between the
HotSwap MBP module and the UPS).
3 - Set switch (53) to Normal position. The red
LED on the HotSwap MBP module goes
31
OFF.