Electric connection

Control and feedback wiring

Unscrew the right gland and pass the cable.

Connect the input signal between terminals 15 and 16. Terminal 15 is the negative polarity (-) and terminal 16 is the
positive polarity (+).

Connect the output signal between terminals 13 and 14. Terminal 13 is the positive polarity (+) and terminal 14 is the
negative polarity (-).

Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Factory setting : by default, 4-20mA input and output signals with normal rotation direction.
Be sure you connect the terminal 15 (-) before the terminal 16 (+)

Learning mode


Switch on the actuator

Press both OPEN and CLOSE buttons until the learning mode is selected, (APPR LED on).

Press CLOSE button. The valve operate into closed position.

When the valve is closed, press both CLOSE and MEM buttons during 2 seconds.

The APPR2 led blinks rapidly and then lights on. The closed position is stored.

Press OPEN button. The valve operate into open position.

When the valve is open, press both OPEN and MEM buttons during 2 seconds.

The APPR1 led blinks rapidly and then lights on. The closed position is stored

Exit the learning mode by simultaneously pressing the OPEN and CLOSE buttons to the POSI mode.