INSTALLATION
Fig. 9.8
Mounting plate for 17-050 NMWI.
• Case B: Running the pipework out of either side or the
bottom of the unit.
In this case holes do not have to made in the wall since the
indoor unit body has knock outs which can be removed to
allow the pipes to exit the unit: choose the most convenient
one for the desired outlet position (see Figures 9.7).
- Carefully break the knock out in the casing using pliers.
4
3
2
EN
Fig. 9.9
Openings for the installation of the pipes.
Legend
1
Exit for left piping
2
Securing with adhesive tape
3
Exit for indoor piping
4
Exit for right piping
9.3.5
Correct installation of indoor unit
refrigerant pipe work
If installing the rear exiting piping:
• Place a seal ring for the hole in the piping and insert the
coolant pipes with the condensed water pipe through the
hole.
• Remember to seal the hole inside and out properly after
installing the pipes.
• Carefully bend the installation pipe in the right direction,
taking care not to overbend or kink the pipe.
- 14 -
1
SDH17-MNW-I_EN - 03/13 - Saunier Duval