3.1.2
Automatic configuration of inputs/outputs and setting the parameters
To display and set the parameters, enter the configuration menu as described above, and then enter the second password for parameter P92
(password 66).
AHU 100% outside air
To simplify the configuration, one of the 3 automatic configurations can be used:
Switch the device OFF
Set parameter 91 to one of the values shown in the table below
Input /
Output
ID1
On-Off
ID2
Cooling-heating
ID3
Serious alarm
ID4
Antifreeze alarm
ID5
Filter alarm
B1
Outlet temperature
B2
Heating coil temperature
B3
Outside temperature
DO1
Single-speed outlet fan
AO1
Cooling valve
AO2
Heating valve
DO3
Outside damper
DO4
Output deactivated
Then on the "acqua" terminal set the parameters for the inputs/outputs that change compared to the chosen configuration.
Code +050001260 – Rel. 2.0 – 22/01/08
P91=44
AHU 100% outside air - 0-10V valves
Fig. 3.b
P91=45
AHU 100% outside air - 0-10V valves
On-Off
Cooling-heating
Serious alarm
Antifreeze alarm
Filter alarm
Outlet temperature
Heating/cooling coil temperature
Outside temperature
Single-speed outlet fan
Heating /cooling valve
Outside air damper
Electric heater
Bypass damper
17
AHU with recirculation
P91=46
AHU with recirculation - 3 point valves
On-Off
Cooling-heating
Serious alarm
Antifreeze alarm
Filter alarm
Outlet temperature
Heating/cooling coil temperature
Outside temperature
Single-speed outlet fan
Open heating / cooling valve
Close heating / cooling valve
Open outside air damper
Close outside air damper
MasterAria