INSTALLATION AND SERVICE INSTRUCTIONS FOR FIREBALL ® MODELS FB2PSTX AND
It is important to follow all instructions shipped with this product. This device is to be installed by a trained
electrician who is thoroughly familiar with and will follow all applicable national and local codes in the country of
use.
This device should be considered a part of the warning system and not the entire warning system.
The selection of the mounting location for the device, its controls and the routing of the wiring is to be accom-
plished under the direction of the facilities engineer and the safety engineer. In addition, listed below are some
other important safety instructions and precautions you should follow:
• Read and understand all instructions before installing or operating this equipment.
• Never alter the unit in any manner. Safety in hazardous locations may be endangered if additional openings or
other alterations are made in units specifically designed for use in these locations.
• Do not connect this light to the system when power is on.
• After installation, ensure that all set screws and threaded joints are properly tightened.
• Keep unit tightly closed when in operation.
• After installation, test the light system to ensure that it is operating properly.
• After testing is complete, provide a copy of this instruction sheet to all personnel.
• Establish a procedure to routinely check the light system for proper activation and operation.
Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death to
you or others.
I. GENERAL.
The Models FB2PSTX and FB2PSTX-I Strobe Light are explosion-proof visual signaling devices UL Listed for
hazardous and marine locations. Underwriters Laboratories has investigated the Model FB2PSTX and
FB2PSTX-I to ensure they comply with TYPE 4X (watertight and corrosion resistant) and IP66 (dust-tight and
heavy seas) enclosure requirements.
The Model FB2PSTX is available for 12-24V dc, 120V ac, 50/60 Hz, and 230-240V ac, 50/60 Hz. The Model
FB2PSTX-I is available for 24VDC only.
II. UNPACKING.
Damaged globes can lead to explosions which could result in serious injury or death.
After unpacking the Model FB2PSTX or FB2PSTX-I, examine it for damage that may have occurred in transit.
If the equipment has been damaged, do not attempt to install or operate it, file a claim immediately with the
carrier stating the extent of the damage. Carefully check all envelopes, shipping labels and tags before removing
or discarding them. Disposal of all shipping materials must be carried out in accordance with national and local
codes and standards.
III. INSTALLATION.
The glass globe is part of the explosion-proof housing. If the globe requires added protection,
a separately purchased metal guard (Part No. DGFBX) can be readily attached.
Hazardous Location mounting position limitation of this light is the globe must be facing down when installed.
In all countries, the wiring must comply with all national and local codes and standards.
A. See figure 1. Install the fixture mount on the desired support surface using the four (4) 0.31 inch [8.0 mm]
mounting slots. Use customer supplied fasteners suitable for the surface to which the device will be mounted.
FOR USE IN HAZARDOUS AND MARINE LOCATIONS
SAFETY MESSAGE TO INSTALLERS,
USERS AND MAINTENCE PERSONNEL
FB2PSTX-I
NOTE