Output charts water PA2200C
Type
Fan
Airflow
position
[m
PA2210CW
max
1200
min
700
PA2215CW
max
1800
min
1000
PA2220CW
max
2400
min
1400
Type
Fan
Airflow
position
[m
PA2210CW
max
1200
min
700
PA2215CW
max
1800
min
1000
PA2220CW
max
2400
min
1400
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
2
) Nominal output at given supply and return water temperature.
See www.frico.se for additional calculations.
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +32 °C
Output
Return
water
/h]
[kW]
temp.
3
[°C]
5,7
55,0
3,3
46,3
8,6
52,5
4,8
43,3
11,4
53,4
6,7
44,9
Supply water temperature: 55°C
Room temperature: +18 °C
Outlet air temperature: +29 °C
Output
Return
water
3
/h]
[kW]
temp.
[°C]
4,5
46,5
2,6
40,0
6,7
44,2
3,7
37,4
9,0
45,2
5,2
38,9
PA2200C
Water temperature: 60/40 °C
Room temperature: +18 °C
Water
Pressure
Output *
flow
drop
[l/s]
[kPa]
[kW]
0,28
64,4
3,7
0,06
4,0
2,7
0,28
36,5
6,1
0,07
3,1
4,3
0,42
39,7
7,8
0,11
3,5
5,6
Water temperature: 55/35°C
Room temperature: +18 °C
Water
Pressure
Output *
flow
drop
[l/s]
[kPa]
[kW]
0,13
16,3
2,8
0,04
2,3
2,0
0,15
12,5
4,9
0,05
1,9
3,4
0,22
12,8
6,0
0,08
2,1
4,3
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
27,0
0,05
2,5
29,3
0,03
1,4
28,0
0,07
3,6
30,6
0,05
1,9
27,5
0,09
2,8
29,8
0,07
1,6
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
24,9
0,03
1,6
26,5
0,02
0,9
25,9
0,06
2,4
27,9
0,04
1,3
25,4
0,07
1,8
27,1
0,05
1,0
15