HUBBELL 60-100 AMP CIRCUIT-LOCK
GENERAL INFORMATION
1. NOTICE: For installation by a qualified electrician in accordance with national and local electrical codes
and the following instructions.
2. CAUTION: RISK OF ELECTRIC SHOCK. More than one disconnect switch may be required to de‑energize
this equipment before servicing. Disconnect ALL power supplies to enclosure before exposing interior.
3. NOTICE: Separate overcurrent protection must be provided in accordance with National Electrical Code
Article 220 or Canadian Electrical Code, Section B, as appropriate.
4. Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical amperes, 600VAC
maximum. Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical amperes,
600 VAC maximum when protected by Class J fuses rated 100 amperes maximum. Auxiliary contact (if
installed) is suitable for use in a circuit not capable of delivering more than 3,000 rms symmetrical amperes,
600 VAC maximum.
5. This enclosure includes a lockout provision: ON‑OFF control knob (in the OFF position) accepts up to 5/16
inch (8 mm) diameter shackle of a suitable padlock or Lockout device to isolate energy from the connected
equipment as a method of compliance to OSHA Lockout/Tagout Regulation 29 CFR Part 1910.147. This
feature does NOT isolate the power supplied to the enclosure during internal servicing of the enclosure.
CLEANING PROCEDURES
6. Follow the general cleaning procedures established by your facility for your specific application.
7. This product is certified by NSF
cleaning practice is recommended for this product:
CAUTION: Use only chemicals and cleaning solutions that are safe for use with plastics and rubber gaskets.
CAUTION: Risk of electric shock. Do not clean this product while undergoing electrical maintenance or service.
a. Use hose directed water or cleaning solution to remove any collected soil or contaminants from behind this enclosure. Care must be
exercised to apply the water spray in such a manner to completely wash the area between the enclosure and the wall onto which it is
mounted.
b. Use hose directed water or cleaning solution to wash away soil or contaminants from the exterior surfaces of the enclosure.
c. CAUTION: Do not direct or concentrate high pressure water or cleaning solution on
the lid and box gasket seams, switch handle area or on any applied labels.
d. After using hose directed water or cleaning solutions, use a clean damp cloth to manually
re‑move any soil or other contaminants from the gasket seam area, handle area or
other necessary areas.
e. Use a dry clean cloth to wipe away any excess water.
INSTALLATION INSTRUCTIONS
This enclosure may be mounted for top, bottom, back or dual conduit entrances.
A. MOUNTING INSTRUCTIONS
1. For Type 4X and Type 12 applications, enclosure must be mounted by means of
mounting feet. DO NOT drill, punch or nail mounting holes through the enclosure.
2 Mounting feet will accept up to ¼" or 6 mm screws (not provided). Mounting pattern is
shown in Fig. M‑1.
3. Remove the enclosure cover. Use caution that the sealing O‑rings under the screw
heads are not lost.
4. Drill or punch at the desired conduit entrance location(s): (drill spots shown in Fig. M‑2)
a. 1‑3/8 inch (34.9 mm) diameter for 1 inch TRADE SIZE.
b. 1‑3/4 inch (44.4 mm) diameter for a 1‑1/4 inch TRADE SIZE.
5. Use ONLY Listed/Certified conduit hub rated for Type 4X and Type 12 applications such as RACO #1705 (two supplied).
6. Install the conduit hub. Be sure that the "O" ring is properly seated in its groove. Tighten the conduit hub.
7. Any unused conduit entrance holes must be sealed with Listed/Certified closure plugs rated Type 4X and Type 12.
8. Use of user‑installed conduit entrances above the switch are not recommended in applications where condensation may be present in conduit.
When using the top feed conduit entrance, drip loops must always be formed as indicated in figs. M‑2 and M‑3.
9. If required use ONLY a Listed / Certified Breather Drain rated for Type 4X and Type 12 applications such as HLS Type Be.20.S.NT. Punch
or drill a .796 inch diameter hole on the drill spot through the bottom wall of the enclosure (see Fig M‑3).
WIRING INSTRUCTIONS
1. Select conductors having 90°C or higher rated insulation and sufficient ampacity in accordance with the 75 °C column of National Electrical
Code® Table 310‑16 or Canadian Electrical Code, Table 2.
2. CAUTION: USE COPPER CONDUCTORS ONLY.
3. DO NOT TIN CONDUCTORS.
4.
TABLE 1
60A
5.
Switch
#2 to #10 AWG
Ground
#6 to #16 AWG
Neutral
#6 to #14 AWG
Auxiliary
#14 to #18 AWG
Contact
10. Tighten the grounding buss mounting screw to 21.2 pound•inches (2.4 N•m).
11. Reinstall the cover. The handle must be in the OFF position. Tighten the four cover screws to 24 pound•inches (2.7 N•m). Make sure the
sealing O‑rings are in place under the screw heads.
12. An additional DANGER label (D64558) has been supplied loose with this product as a convenience. Apply label to the outside of the front
cover (see figure M‑1) if the product application does not pose the risk of the label being removed through cleaning, hose down or any
other means.
13. Consult factory for auxiliary contact availability.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2521
(PAGE 1)
®
International for use in food processing Splash Zone Areas, the following
100A
#2 to #10 AWG
#6 to #16 A
#2 to #12 AWG
#14 to #18 AWG
02/13
®
Make sure the connected equipment rating does not exceed the rating of this device.
See GENERAL INFORMATION (#4) regarding overcurrent protection.
Terminal capacity:
6. Strip conductor insulation ½" (13 mm).
7. Select the proper wiring diagram. Loosen terminal screws. Insert conductors fully
into proper terminals.
8. Tighten terminal screws as follows:
a. SWITCH terminal capacity: 50 pound•inches (5.7 N•m).
b. GROUND terminals: 35.4 pound•inches (3.9 N•m)
Neutral terminals 60A: 35.4 pound•inches (3.9 N•m)
Neutral terminals 100A: 44.3 pound•inches (5.0 N•m)
c. Auxiliary Contact terminals: 10‑12 pound•inches(1.2‑1.4 N•m)
9.
TAKE CAUTION THAT THERE ARE NO STRAY WIRE STRANDS.
DISCONNECT SWITCH
®
This manual motor controller carries
a maximum rating of:
60 A and 100 A
7.5 HP (5.6 kW)
15 HP (11.19 kW)
30 HP (22.37 kW)
30 HP (22.37 kW)
50 HP (37.28 kW)
50 HP (37.28 kW)
English
600 VAC
120 VAC, 1Ø
200‑240 VAC, 1Ø
480 VAC, 1Ø
200‑240 VAC, 3Ø
480 VAC, 3Ø
600 VAC, 3Ø