DESCRIPTION
The H-MOSS® sensor is an intelligent self-adapting occupancy
sensor that is designed to replace existing wall switches.
SPECIFICATIONS
• 1000 sq. ft. coverage area (Models: AP and AD)
• 400 sq. ft. coverage area (Models: AU)
• Single or Dual Circuit 120/277VAC, 50/60Hz operation
• Electrical Ratings: (Each Output Separately)
120VAC – 800W Incandescent, 1000W Ballast, 1/4 HP
277 VAC – 1800W Ballast, 1/4 HP
• Adjustable Time Delay: 4-30 minutes, self-adapts based on
occupancy
• Light Level Adjustment (Circuit B output on Dual Circuit versions):
10 to 500FC
• UL, cUL Listed
PRECAUTIONS
CAUTION: RISK OF ELECTRICAL SHOCK. Turn power off at service
panel before beginning installation. Never wire energized electrical
components.
CAUTION: USE COPPER CONDUCTOR ONLY
Read and understand all instructions before beginning installation.
NOTICE: For installation by a licensed electrician in accordance with
National and/or local Electrical Codes and the following instructions.
NOTICE: For indoor use only.
Confirm device ratings are suitable for application prior to installation.
Use of device in applications beyond its specified ratings or in
applications other than its intended use may cause an unsafe
dition and will void manufacturer's warranty.
NOTICE: Do not install if product appears to be damaged.
NOTICE: Connect to field wiring rated for 60°C or greater.
INSTALLATION
1.Turn power OFF at the service panel.
2.Remove the old switch(es) if applicable.
3.Wire as shown in the WIRING DIAGRAMS section. Figures 1 and 2
denote wiring method for Leakage to Ground Sensors (NOTE: A
secure ground is required for proper operation). Figures 3 and 4
denote wiring method for Neutral Wiring Sensors.
4.Install sensor in wall box using mounting screws provided.
5.Restore power to the sensor and allow it to initialize (up to 2 minutes).
6.Sensor is factory configured to provide the most energy savings. If
additional adjustments are required, see the ADJUSTMENTS
section.
7.If daylight harvesting is desired, calibrate the sensor's photocell as
described in the PHOTOCELL CONTROL section.
8.Install a decorator style wall plate (not included).
TEST MODE
1.Make sure lights are ON
2.Press and hold the ON/OFF button. Lights will cycle OFF then back
ON. Release the ON/OFF button.
• For dual circuit sensors, press and hold the ON/OFF button for
Circuit A.
• For sensors without buttons, remove the cover (see ADJUSTMENTS
section) and press and hold the Test Button.
3.Sensor is now in Test Mode (NOTE: While in Test Mode the sensor
will operate in Automatic ON/Automatic OFF mode). Vacate room;
lights should turn OFF after 5 seconds. Wait 5 seconds after turn
OFF before re-entering space. Step back into room, lights will turn
back ON. Repeat walk test as necessary to confirm sensor is
operating and detecting in the area as desired. Sensor will flash red
and/or green LED while moving to indicate Passive Infrared (PIR) or
Ultrasonic occupancy detection respectively. NOTE: Sensors with
ultrasonic technology can be very sensitive and may require more
than 5 seconds of no movement before turning lights off.
4.To exit Test Mode, press any button.
NOTE: Sensor will automatically exit Test Mode after sixty (60)minutes.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2611
Page 1
H-MOSS
Motion Switching System
®
Passive Infrared / Ultrasonic Occupancy Sensors
Installation and Operating Instructions
04/15
COVER RELEASE
CATCH
LINE CIRCUIT
BLACK
PHOTOCELL
PUSH BUTTON
GROUND
CONNECTION
COVER RELEASE
CATCH
LINE CIRCUIT
BLACK
PHOTOCELL
PUSH BUTTON
con-
GROUND
CONNECTION
COVER RELEASE
CATCH
LINE CIRCUIT
BLACK
PHOTOCELL
PUSH BUTTON
NEUTRAL
WHITE
GROUND
CONNECTION
COVER RELEASE
CATCH
LINE CIRCUIT
BLACK
PHOTOCELL
PUSH BUTTON
NEUTRAL
WHITE
GROUND
CONNECTION
WIRING DIAGRAMS
RED
LOAD 1
FIGURE 1
BUTTON A
MULTI-TECH, DUAL
(TEST BUTTON)
CIRCUIT, GROUND
BUTTON B
CONNECTION
BLUE
LOAD 2
RED
LOAD
FIGURE 2
MULTI-TECH, SINGLE
BUTTON A
(TEST BUTTON)
CIRCUIT, GROUND
CONNECTION
RED
LOAD 1
FIGURE 3
BUTTON A
ULTRASONIC, DUAL
(TEST BUTTON)
CIRCUIT, NEUTRAL
BUTTON B
CONNECTION
BLUE
LOAD 2
RED
LOAD
FIGURE 4
(TEST BUTTON
PASSIVE INFRARED,
LOCATED
SINGLE CIRCUIT, NO
UNDER COVER)
BUTTON, NEUTRAL
CONNECTION
English
®