GB
2.6
Technical data
2.6.1
Refrigeration data
Cooling capacity at * / **
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication: Switch cabinet interior temperature
(factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, interior circuit
Condensate separation
2.6.2
Electrical data
Rated operating voltage * / ***
Rated frequency *
Functional range
Power consumption *
Rated current *
Upstream fuse ***
Cooling capacity at A35/ A20 * / **
Cooling capacity at A35/ A35 * / **
Cooling capacity at A35/ A50 * / **
2.6.3
Dimensions
DTS height
DTI height
Width
Depth with cover (standard) DTS
Depth with cover (standard) DTI
DTI installation depth
Weight
Installation position
Unit construction
2.6.4
Other unit data
Anti-corrosion protection
Protection type
*
Data on the type plate.
***
Max. rated current UL at 60 Hz.
Operating Manual DTS and DTI 6X1E Premium Controller X-Series (XC) 086100018 © Pfannenberg GmbH
Designation
Designation
P
A35 / A35
I
nom max
Designation
Designation
Q
0
+15°C (+59°F) to +55°C (+131°F)
+25°C (+77°F) to +45°C (+113°F)
el
Q
0
Q
0
Q
0
DTI: 70 kg
Standard: Galvanized, electrostatic powder-
coated (200°C)
Variant: Stainless steel cover
When used as intended:
IP 54 against the switch cabinet (EN 60529).
IP 34 against the environment (EN 60529).
**
Use of optional filter mats reduces the cooling capacity.
**** With a change to the rated operating voltage, adapt the
upstream fuse; see
Model DTI/DTS 6X1E
1000 W – 2600 W
R 134a
650 g
+35°C (+95°F)
> +50°C (+122°F)
990 m³/h
Condensate evaporator
Model DTI/DTS 6X1E
230 V
AC 50 / 60 Hz
DIN IEC 60038
1117 W
5.5 A
10 A
3500 W
2600 W
2500 W
Model DTI/DTS 6X1E
1547 mm
1538 mm
485 mm
278 mm
218 mm
60 mm
DTS: 75 kg
Vertical
Standard: Steel sheet
Model DTI/DTS 6X1E
Adapting the
upstream fuse.
Page 12 / 40