General assembly requirements

The following general requirements must be followed for safe and reliable operation of the cooling units:
 The place where the switch cabinet is mounted must be selected so as to guarantee adequate ventilation of the
cooling unit. A minimum clearance of 200 mm between units and from the nearest wall must be observed.
 Installed components in the switch cabinet must not impede air circulation.
 Secure the switch cabinet against tipping.
 Ensure that provided hinges can support the additional weight of the cooling unit.
 Assembly of the cooling unit can take place with and without an external unit cover.
 Protect the installation location from heavy contamination with covers.
3.4.2

Mounting M8 jack rings

WARNING
Danger of accidents due to unapproved crane transport
Movement of switch cabinets with integrated cooling units can result in accidents.
 Lifting by M8 jack rings is only permitted for the cooling unit.
 Ensure that jack rings and unit threads are not damaged or deformed.
 Only use jack rings with an adequate thread length and ensure that they are securely seated.
The cooling units have threads for M8 jack ring installation. M8 jack rings can be installed in cooling units for crane
transport.
Item
Designation
1
DTS cooling unit M8 jack rings
Requirements
-
The factory-provided packaging has been removed from the cooling units.
-
Observe the minimum screw depth of the M8 jack rings.
-
M8 crane eyes and cooling unit threads must be free from damage (corrosion and deformation).
-
The unit cover screws (2) have been removed.
Procedure
 Screw in the two M8 jack rings (1) completely with the appropriate thread depth.
 Check to ensure the proper approved seating of the M8 jack rings in the cooling unit.
The M8 jack rings are installed in the cooling unit and the unit can be moved.
Operating Manual DTS and DTI 6X1E Premium Controller X-Series (XC) 086100018 © Pfannenberg GmbH
1
Figure
- DTI/DTS cooling unit M8 jack rings
6
Item
1
2
Designation
2
Unit cover screws
Page 15 / 40

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Dti 6x1e serieDts 6x1e serie

Tabla de contenido