GENERAL INFORMATION
Leak-Seeker
I Specifications
®
Sensor:
State of the art E_MOS
Gases:
Detects refrigerants including those with
hydrocarbon components (CFC, CH2F2,
HCFC, HFC, HFO, NH3, HC. Hydrogen
trace gas in 95% N2, 5% H2 mixture A2L
refrigerants).
CAUTION: This leak detector is not
intrinsically safe. Use in well ventilated areas.
Sensitivity:
Better than a 0.1 oz / year (3 g / annually)
for all common refrigerants, including
R-410a, R-404a and R-407a
Leak Indicators:
Extended tone range audible alarm indi-
cates the relative size of the leak in the
Progressive Alarm mode. Single high
pitch tone audible alarm in the Threshold
Alarm mode signals the presence of a leak.
Audible alarm can be turned ON or OFF by
double-clicking the START button. Eight
LED bar graph indication signaling the
relative size of the leak in the Progressive
Alarm mode. Solid 8 LED bar turns on in
the Threshold Alarm mode when a leak is
present
Operating
-18 to 60˚C (0 to 140˚F)
Temperature:
Power:
Three size "C" alkaline batteries (NEDA/
ANSI 14A)
Battery Life:
50 hours minimum at 77˚F (25˚C). Battery
life depends on cell chemistry and ambi-
ent conditions. Alkaline batteries provide
longest life. Cold ambient conditions de-
crease battery life. The Leak-Seeker
turns itself off after 10 minutes of inactivi-
ty—START button not pressed—to further
prolong battery life
Dimensions:
Instrument (L x W x H): 10" x 2.3" x 2"
254mm x 59mm x 51mm
Probe:
15" (380mm) long, .25" (6.4mm) diameter
Weight:
1 lb 2 oz (500 g)
Certifications:
Complies with European Standard
EN14624:2012
3