Active Sensors
Temperature sensor 1
Temperature sensor 1
Temperature sensor 2
Temperature sensor 1
Temperature sensor 2
Temperature sensor 3

5.5 - Cooling System

Operation parameters related to the cooling output (COOL 1)
Fun
Differential to Turn On cooling device
F01
Differential to Turn Off cooling device
F02
High Humidity to Force Cooling OFF
F03
High Humidity Differential to Restart Cooling
F04
Cooling Output ON Time
F05
Cooling Output OFF Time
F06
F01 - Differential to turn on cooling device
Temperature difference between setpoint and
F02 - Differential to turn off cooling device
Temperature difference to turn off cooling device.
F03 - High Humidity to Force Cooling OFF
Maximum air humidity before turning the cooling output OFF.
F04 - High Humidity Differential to Restart Cooling
Maximum air humidity differential to allow reactivating the cooling output.
F05 - Cooling Output ON Time
Time period in seconds the cooling output will be ON. If set to "0", the output will be permanently ON.
F06 - Cooling Output OFF Time
Time period in seconds the Cooling output will be OFF.
5.6 - Water Sprayers
Operation parameters related to water sprayer outputs
Fun
Differential to Turn On Water Sprayer 1
Differential to Turn Off Water Sprayer 1
Differential to Turn On Water Sprayer 2
Differential to Turn Off Water Sprayer 2
Humidity to Turn On Water Sprayer 1
Humidity Differential to Turn Off Water Sprayer 1
Humidity to Turn On Water Sprayer 2
Humidity Differential to Turn Off Water Sprayer 2
High Humidity to Force Water Sprayers 1 and 2 OFF
High Humidity Differential to Restart Water Sprayers
Water Sprayer Outputs ON Time
Water Sprayer Outputs OFF Time
N01 - Differential to Turn On Water Sprayer 1
Temperature difference between setpoint and average temperature above which the Water Sprayer 1 Output will be activated.
N02 - Differential to Turn Off Water Sprayer 1
Temperature difference to turn off the Water Sprayer 1 Output.
N03 - Differential to Turn On Water Sprayer 2
Temperature difference between setpoint and average temperature above which the Water Sprayer 2 Output will be activated.
Distribution of outputs according to active sensors
Temperature sensor 1
Temperature sensor 2
Heating 1 Output
Heating 2 Output
Heating 3 Output
Heating 1 Output
Heating 2 Output
Heating 3 Output
Heating 1 Output
Heating 2 Output
Description
desired temperature
above which the cooling output will be activated.
(WAT SPRAY 1
and
WAT SPRAY 2
Description
31
Temperature sensor 3
Heating 3 Output
CELSIUS
FAHRENHEIT
Min. Max.
Unit
Standard
Min. Max.
-50.0
50.0
°C
30.0
-90
90
0.1
15.0
°C
1.0
1
27
0
100.0
%UR
50.0
0
100.0
0.1
20.0
%UR
1.0
0.1
20
0
999
seg.
10
0
999
0
999
seg.
10
0
999
)
Standard
Unit
Standard
°F
54
°F
2
%UR
50.0
%UR
1.0
seg.
10
seg.
10
Standard