Technical Specifications - Chauvin Arnoux STATOP 9601 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. TECHNICAL SPECIFICATIONS

Input
Thermocouple
Thermometric resistance
Measurement extent (f.s.)
Accuracy
Cold junction compensation
Sensor breakdown protection
Load resistance
Series mode rejection
Common mode rejection
Sampling
Control
Mode of control
Proportional band
Band offset (reset)
Hysteresis on On/Off
Modulation rate
Control direction
Output
Relay
Logic voltage
Analogue signal 4...20 mA
Setpoint value
Adjustment
Resolution
Accuracy
Repeatability
STATOP 9601
Pt 100Ω to DIN 43.760 or to former
standard JIS C1604 (1981)
0...100°C, 0...300°C, 0...400°C, 0...600°C,
or 0...1200°C, modifiable by internal wiring
±2% f.s.
3 times per second
STATOP 9601
PID or On/Off, selection by internal wiring
-
20 s for models with relay output,
1 s for models with logic output
reverse or direct, selection by internal wiring
STATOP 9601
10 A / 240 V~, resistive load
ask for details
STATOP 9601
by potentiometer on front panel
25
STATOP 9604
type J or K
±1% f.s.
± 0.1°C per K
max. of scale
100Ω max.
60 dB
120 dB
STATOP 9604
2.2% of f.s.
±2,6% autour de la consigne
1% of f.s.
STATOP 9604
10 A / 240 V~, resistive load
24 VDC, 20 mA maximum
ask for details
STATOP 9604
0.2% of f.s.
±2% of f.s.
±0.1% of f.s.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Statop 9604

Tabla de contenido