2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit
AVOID:
● areas where leakage of flammable gas may be expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room directly.
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
● locations where the remote controller will be splashed with
water or affected by dampness or humidity.
● installing the remote controller behind curtains or furniture.
● locations where high-frequency emissions are generated.
DO:
● select an appropriate position from which every corner of the
room can be uniformly cooled.
● select a location where the ceiling is strong enough to
support the weight of the unit.
● select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the installation
manual packed with the outdoor unit.
● allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
4-Way Cassette 60 × 60
1 m
1 m
1 m
1 m
1 m
Fig. 2-1

3. HOW TO INSTALL THE INDOOR UNIT

■ 4-Way Cassette 60 × 60 Type
(Y1 Type)

3-1. Preparation for Ceiling Suspension

This unit uses a drain pump. Use a carpenter's level to check
that the unit is level.

3-2. Mounting the Suspension Bolts

(1) Fix the suspension bolts securely to the ceiling using the
method shown in the diagrams (Figs. 3-1 and 3-2), by
attaching them to the ceiling support structure, or by any
other method that ensures that the unit will be securely and
safely suspended.
(2) Follow the diagram to make the holes in the ceiling. (Refer
to Fig. 3-2)
Hole-in-anchor
Hole-in-plug
Ceiling opening dimensions
Suspension bolt pitch
(3) Determine the pitch of the suspension bolts using the
supplied full-scale installation diagram. The diagram shows
the relationship between the positions of the suspension
fitting, the unit, and the panel.
Power supply port
6
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
600
534
Drain tube
575
connection port
53
160
170
(outer dia ø26)
Refrigerant tubing joint
(liquid side)
ø6.35 (flared)
Fig. 3-1
Unit: mm
Fig. 3-2
Unit: mm