5.6 Electric Data
Voltage [ V ] / [Hz]
Power supply /
30AJ
Frequency
Unit
Nominal
Min.
04
220/60
198
380/60
342
05
220/60
198
380/60
342
10
220/60
198
380/60
342
Important notes
Dados obtidos do catálogo técnico de compressores do Fornecedor
1.
Data from the supplier's technical catalog.
2.
RLA, KW, RLA TOTAL and kW TOTAL refer to nominal operation data with the unit in operation. Suction temperature: 45°F (7.2°C) and
condensation temperature: 130°F (54.4°C) - ARI conditions.
3.
MOPA values shown in the table were calculated taking into consideration the maximum operation values of the unit.
4.
Values show in the KVAr column be dimensioned to the compressors when is necessary to correct the POWER FACTOR to 0,92.
5.
All compressors are Scroll.
Legends
RLA
Nominal Current (Rated Load Amps).
LRA
Locked Rotor Current (Locked Rotor Amps).
MOPA
Maximum recommended capacity for the protection of the fuse against short circuit.
kW
Consumed Rated Power.
FP
Power Factor (without correction to 0.92)
KVAr
Recommended reactive power for the sizing of the bank of capacitors(0.92).
58
Compressor
Technical Data
Max.
RLA [A]
LRA [A]
kW
ZR47
242
14,3
91,0
4,2
418
7,2
46,0
4,2
ZR57
242
17,2
124,0
5
418
8,2
59,6
5
SZ120
242
33,1
237,0
10,8
418
19,8
160,0
10,8
Technical Data
FP
KVAr
QTDE
RLA [A]
0,76
2,5
1
1,3
0,87
1
1
1,3
0,76
2,1
1
1,3
0,42
1
1
1,3
0,86
5
1
2,2
0,83
5
1
2,2
Fan
Additional
technical data
Circuit A
RLA
kW
P [CV]
TOTAL
Total
[A]
15,6
1/6
0,123
8,5
1/6
0,123
18,5
1/6
0,123
9,5
1/6
0,123
35,3
1
0,75
22,0
1
0,75
kW
MOPA
TOTAL
[A]
[W]
4,3
25
4,3
16
5,1
25
5,1
25
11,5
50
11,5
40