Technical data
Type
Power supply
Nominal current
Nominal force
Nominal locking force
Service time
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Emission sound pressure level LpA ≤ 51 dB(A) (≤ 60,5 dB(A))
Nominal stroke length* / **
Additional functions **
* Adjustable with PLP 1
Normal operation =
SHEV- fast running =
Forces
ZA-0300 ZA-0800 ZA-1000 ZA-1500
OPEN
300 N
800 N
CR III
300 N
800 N
CR II
300 N
800 N
CR I
300 N
800 N
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive protection. The
closing speed in closure Range 2 and 1 is reduced to
5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
6/16
ZA-1-PLP
ZA-0300 (-HS)
24 V DC, ±15%
0,5 A (1,2 A)
300 N
1100 N
>20 000 double strokes
30 % (With cycle time 10 minutes)
Aluminium powder-coated (~RAL 9006), polycarbonate
IP 65 ("-W" = IP 54)
-5 ... +75°C
30 min / 300°C
See type plate
Closing edge protection activated (3 stroke repeatings)
** Programmable with PLP 1 and SCS
1000 N
1500 N
All forces
1000 N
1000 N
1000 N
1000 N
+ approx. 20 % switch-off reserve
800 N
800 N
(temporary)
ZA-0800 (-HS)
ZA-1000 (-HS)
24 V DC, ±15%
24 V DC, ±15%
1,0 A (2,0 A)
1,2 A (2,2 A)
800 N
1000 N
Running speed and forces
Main closing edge
English
ZA-1500 (-HS)
24 V DC, ±15%
1,4 A (2,5 A)
1500 N
99.824.29 2.0/11/17