Technical data
Type
Power supply
Nominal force
Nominal locking force
Lifetime
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Emission sound pressure level
Nominal stroke length *
Additional functions *
* Programmable with software SCS
Running speed
and forces
Normal operation =
SHEV- fast running =
2x 300** N, 11,8 mm/s =
"-HS" 12,2 mm/s
** + approx. 20 % switch-off reserve (temporary)
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
6/16
KA 66 TW-DF
KA 66/xxx-TW
24 V DC / ±15% / 2,0 A
2x 300 N
2x 1500 N
>20 000 double strokes
30 % (With cycle time 10 minutes)
Aluminium powder-coated (~RAL 9006)
IP 32 (With covering stoppers delivered with bracket sets)
-5 ... +75°C
30 min / 300°C
LpA ≤ 70 dB(A)
See type plate
Closing edge protection activated (3 stroke repeatings); Locking relief activated
=
English
99.824.41 1.4/05/18