Elementos de protección
Curva de protección de motor (ejemplo 2 sin RTD)
Underload
trip level
60% full-load
amperes
Underload run
delay: 5 Sec.
Motor running
with load
Underload
start delay
20 Sec.
Jam trip level
180 % full-load
amperes
Jam start delay
15 Sec.
Motor starting current
(locked rotor condition)
6.1 times
full- load amperes
541
MRMV4
Ultimate trip
level: 100 %
full-load amperes
Note: I is a
combination of
positive (I
) and
1
negative (I
)
2
sequence
motor currents
Max. allow.
locked-rotor
amperes:
6 .1 times full-
load amperes
Stall time:
15 Sec.
Instantaneous
overcurrent:
12 times full-
load amperes
Instantaneous
overcurrent:
start delay set
for 2 cycle
múltiplos de Ib
DOK-HB-MRMV4-2ES