3.4
EXTERNAL
SENSOR
(fig. 15)
If. there. is. an. external. sensor,. the. heating.
settings.SET.can.be.taken.from.the.climatic.
curves.according.to.the.external.temperatu-
re.and,.in.any.case,.limited.to.with.the.range.
values. described. in. point. 3.3. (parameters.
PAR.25.for.zone.1.and.PAR.26.for.zone.2).
The.climatic.curve.to.be.set.can.be.selected.
from.a.value.of.3.and.40.(at.step.1).
Increasing. the. steepness. of. the. curves. of.
fig..15.will.increase.the.output.temperature.
as.the.external.temperature.decreases.
3.5
CARD
FUNCTIONING
The. electronic. card. has. the. following. fun-
ctions:
–. Antifreeze. protection. of. the. heating. and.
sanitary.water.circuits.(ICE).
–. Ignition.and.flame.detection.system.
–. Control. panel. setting. for. the. power. and.
the.gas.for.boiler.functioning.
–. Anti-block.for.the.pump.which.is.fed.for.a.
few.seconds.after.24.hours.of.inactivity.
–. Antifreeze. protection. for. boilers. with. an.
accumulation.boiling.unit.
–. Chimney. sweep. function. which. can. be.
activated.from.the.control.panel.
–. Temperature. which. can. be. shifted. with.
the.external.sensor.connected..
. It.can.be.set.from.the.control.panel.and.
is. active. on. the. heating. systems. of. both.
circuit.1.and.circuit.2.
–. Management.of.two.independent.heating.
circuit.systems.
–. Automatic.regulation.of.the.ignition.power.
and.maximum.heating...Adjustments.are.
managed.automatically.by.the.electronic.
card.to.guarantee.maximum.flexibility.in.
use.of.the.system.
–. Interface. with. the. following. electronic.
systems:. remote. control. SIME.HOME.
code.8092280/81,.thermal.regulator.RVS,.
connected. to. a. management. card. of. a.
mixed.zone.ZONA.MIX.code.8092234.and.
card.solar.INSOL.code.8092235...
. NOTE: If using CR 53 or RVS set parame-
ter 10 to 2 or 3 (PAR 10 = 2 or 3).
–. Function.anticondensig,.preheat.the.body.
("+". sign. in. front. of. the. main. digits). and.
anti.inertia.
3.6
TEMPERATURE
DETECTION SENSOR
Table 3. gives. the. values. of. the. electrical.
element. (
). obtained. on. the. heating. and.
Ω
sanitary. water. sensors. according. to. the.
variations.in.temperature..
When the heating sensor (SM) is interrup-
ted, the boiler will not function for both
services.
With the D.H.W. sensor (SS) interrupted,
ATTENTION: curves are calculated at an ambient
temperature of 20°C. The user can act on the boiler
controls to change the environment set for which the
bend has been calculated by ±5°C.
the boiler functions but will not made the
power modulations for the D.H.W.
TABLE 3
. Temperature.(°C).
Resistance.(Ω)
.
20.
12.090
.
30.
8.313
.
40.
5.828
.
50.
4.161
.
60.
3.021
.
70.
2.229
.
80.
1.669
3.7
ELECTRONIC IGNITION
Ignition.and.flame.detection.is.controlled.by.
a.single.electrode.on.the.burner.which.gua-
rantees. reaction. in. the. case. of. accidental.
extinction.or.lack.of.gas.within.one.second.
3.7.1
Functioning cycle
Burner. ignition. occurs. within. max.. 10.
seconds.after.the.opening.of.the.gas.valve..
Ignition.failure.with.consequent.activation.of.
block.can.be.due.to:
–. Lack of gas
The.ignition.electrode.persists.in.dischar-
ging. for. max.. 10. seconds.. If. the. burner.
does.not.ignite,.the.anomaly.is.signalled.
. This.can.happen.the.first.time.the.boiler.
is.switched.on.after.a.long.period.of.inac-
tivity.due.to.the.presence.of.air.in.the.gas.
pipes.
..
It.can.be.caused.by.a.closed.gas.tap.or.by.
a.broken.valve.coil.(the.interruption.does.
not.allow.for.opening)..
–. The electrode does not discharge.
. In.the.boiler,.only.the.opening.of.the.gas.
to. the. burner. can. be. detected.. After. 10.
seconds.the.anomaly.is.signalled.
.. It. can. be. caused. by. an. interruption. in.
the. electrode. wire. or. if. it. is. incorrectly.
anchored.to.the.connection.points..
. Or.the.electrode.may.be.earthed.or.stron-
gly.worn:.it.must.be.replaced..
. Or.the.electronic.card.may.be.defective.
In.the.case.of.a.sudden.lack.of.voltage,.the.
burner. will. immediately. switch. off.. When.
voltage.returns,.the.boiler.will.automatically.
start.up.again.
3.8
FUMES THERMOSTAT
This.is.a.safety.measure.against.the.return.
of. the. fumes. into. the. environment. due. to.
an. inefficient. or. partially. blocked. chimney.
(6.fig..3)..
It. reacts. by. blocking. the. functioning. of. the.
ES
PT
ENG