Heat Pump Systems
Typical Wiring Configurations
NOTE: The "Installer Switch" option will be configured in the next step.
1 HEAT / 1 COOL - No Auxiliary Heat
Set Installer Switch to HP
Rh
24 Volt AC Power
Rc
Connected to Rh with supplied Jumper Wire
O or B Changeover Valve [note 2]
Y1
Compressor Relay
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
2 HEAT / 1 COOL - Including Auxiliary Heat (PRS4210 only)
Set Installer Switch to HP
Rh
24 Volt AC Power
Rc
Connected to Rh with supplied Jumper Wire
O or B Changeover Valve [note 2]
Y1
Compressor Relay (1st stage heating/cooling)
W2
Auxiliary Heat Relay (2nd stage heating) [note 3]
E
Emergency Heat Relay [note 3]
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
NOTES - Heat Pump Systems
[1] If batteries are installed the 24 Volt AC common connection is optional.
[2] Select O for cool active or B for heat active.
[3] Install a field supplied jumper between the W2 and E terminals if
there is no separate emergency heat relay installed.
Provide disconnect and overload protection as required.
Set Installer Switches
4
The Installer switches are located on the back of the thermostat and must
be properly set for this thermostat to operate properly. The reset button
must be pressed after making any changes to these switches.
Factory Setting
Switch
Default Options Comments
CONV / HP
F / C
HE / HG
CONV
CONV
HP
F
F
C
HG
HG
HE
Select for conventional systems
Select for heat pump systems
Select for fahrenheit temperature scale
Select for celsius temperature scale
Select for gas heat
Select for electric heat