3. Type of Grid

This section is for selecting the type of grid and its parameters. Enter via the Display:
Menu > Configuration > Grid/Genset > Type of Grid > Generator
Enter the following parameters for the diesel generator:
Setting
RATED POWER
VAC MIN
VAC MAX
FAC MIN
FAC MAX
Once configured, save the changes.

4. Operation Mode

For the operation of the INGECON SUN STORAGE 1Play in stand-alone installations, it is
necessary to configure the inverter operating mode to "Stand-Alone" mode.
For more information about the operation of this type of installation, see the
"Technical guide for installations with INGECON SUN STORAGE 1Play"
available on the Ingeteam website.
Enter via the Display:
Menu > Configuration > Operation Mode > Mode > Stand-Alone
Enter the following parameters:
Setting
SOC MAX
SOC GRID
SOC MIN
SOC DESCX
SOC RECX
CHARGING POWER
Once configured, save the changes.
ABH2013IQM15_.docx
Installation and configuration of a stand-alone system
Rated voltage of the AC loads supply (V).
Rated frequency of the AC loads output (Hz).
Single-phase system. Configure with the 0 value "Single Phase".
Rated power of the diesel generator set (W). With this parameter, the ISS
1Play estimates the power available for loading the batteries, considering
the consumption of the installation from the diesel generator.
Minimum AC voltage generated by the diesel generator set (V).
Maximum AC voltage generated by the diesel generator set (V).
Minimum frequency generated by the diesel generator set (Hz).
Maximum frequency generated by the diesel generator set (Hz).
Maximum SOC for charging the batteries from the photovoltaic energy (%). A
value of 100% is recommended.
Maximum SOC to stop the diesel generator (%).
Minimum SOC to start the diesel generator (%).
Minimum SOC to fully discharge the batteries, stopping the supply to the loads
(%). A value of 50% is recommended for lead-acid batteries. Please refer to
battery manufacturer for Lithium-ion batteries.
Reboot SOC of supply to the loads using photovoltaic energy (no diesel generator
available) (%). The same value as for SOC MIN is recommended.
Maximum power for charging the batteries from diesel generator (W).