8.4 Level measurement with limited
display range
A third example is level measurement
with limited display range, that means a
tank with 10 m 3 has to be filled up at
most to 8 m 3 and its the level should not
decrease below 1 m 3 . At values > 8 m 3
the dis play shows "hi" and at values <
1 m 3 the display shows "lo".
4 – 20 mA is chosen as input range.
Assign 0 as "displayed value at min. input
signal" to the lo west input level and 10 as
"displayed va lue at max. input signal" to
the highest input level.
Additionally at menu title "min. input
signal" the value which cor re sponds
to the 1 m 3 level, e.g. 5.6 mA is
pro gram med. Do the same with the
va lue which cor re sponds to the 8 m 3
level, e.g. 16.8 mA.
At input levels > 16.8 mA "hi" will be dis-
played and at input levels < 5.6 mA "lo".
Max. input
voltage or
max. input
current can be
shifted inside
the input volt-
age range or
the input cur-
rent range.
Displayed value can be
freely adjusted to the
input value inside the
display range.