Leak Test And Vacuum Drying - LG MULTI V mini R410A Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Refrigerant Piping

Leak Test and Vacuum Drying

1. Leak test
Leak test should be made by pressurizing nitrogen gas to 38.7 kgf/cm
for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test
method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid
pipe, gas pipe and high/low pressure common pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after
completion of nitrogen gas pressurization.
During this test, set DIP switch as Vacuum Mode.
Note:
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is
checked, apply the following correction factor
There is a pressure change of approximately 0.1 kgf/cm
Correction= (Temp. at the time of pressurization – Temp. at the time of check) X 0.1
For example: Temperature at the time of pressurization (38.7 kgf/cm
CAUTION
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must
be at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
38
Outdoor Unit
Nitrogen gas
cylinder
24 hour later: (38.0 kgf/cm
In this case the pressure drop of 0.07 is because of temperature drop
And hence there is no leakage in pipe occurred.
2
(551 psi). If the pressure does not drop
2
(1.4 psi) for each 1°C(2°F) of temperature difference.
2
(541 psi)) is 20°C(68°F)
2
(551 psi)) is 27°C(81°F)

Publicidad

Tabla de contenido
loading

Tabla de contenido