Electrical Wiring
Outdoor Unit
Outdoor Unit
2-Core Shield Cable
CAUTION
• This product have reversed phase protection detector that only works when the power is turned on.
If there exists black out or the power goes on and off which the product is operating, attach a
reversed phase protection circuit locally. running the product in reversed phase may break the
compressor and other parts.
• Use the 2-core shield cables for transmission lines. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate
power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of the
smoothing capacitor.
• Introducing with a missing N-phase or with a mistaken N-phase will break the equipment.
42