Example Connection of Transmission Cable
1. 60Hz
Power supply switch
Single Phase 3wires
(Switch fuse : ELCB)
(L1,L2,GND)
Power supply
208/230V, 60Hz
(Main Switch)
Power supply switch
(Switch fuse)
Power supply
1 Phase
208/230V, 60Hz
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system
consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off
while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Outdoor unit
SODU
IDU
INTERNET
B A
B
A
The GND terminal is a '–' terminal for the central controller, not Ground Line
DRY1 DRY2 GND
12V
3
4
Single Phase 3 wire(L1,L2,GND)
Transmission line (3 line): Wired remote control
Single Phase of power supply line(L1,L2)
Transmission line (2 shield line): Between Indoor Unit and Outdoor Unit
3
4
Installation Manual 47
Electrical Wiring