Status text
Possible cause
H2o.1
• Moisture alarm
moisture de-
tector 1
H2o.2
• Moisture alarm
moisture de-
tector 2
init
• Initialisation
phase
PuMP
• Pumps deactiv-
ated
dt
Active Delta T con-
trol only: The block
temperature is out-
side the defined
temperature range.
• Cooler is still in
the "break-in
phase"
• Fluctuating
ambient tem-
perature
• Insufficient
cooling capa-
city
• Excess/low
temperature
(Flash-
ing)
16
Bühler Technologies GmbH
Action
• Dry
• Check condensate
trap
• Dry
• Check condensate
trap
• Wait
• Reactive pumps
via menu
• Wait to see if the
target temperat-
ure will be
reached
• Check the ambi-
ent temperat-
ure / power sup-
plied
• Process-related:
Adjust alarm lim-
its
• see chapter
"Troubleshoot-
ing"