Installation Manual
EN
Installation
a. The sounder is installed by first mounting the base unit and making the
external wring connections to the base. The head unit then automatically
connects when it is attached to the base.
b. The sounder head is separated from the base by unlocking the four
¼-turn fasteners in the corners of the sounder.
(Recommended screwdriver: Philips No. 2, min 100mm long).
c. Note that the head only fits onto the base one way around. If a beacon
is fitted, care should be taken when mounting the base to ensure that
the beacon will be positioned in the desired orientation after the
sounder is attached
Wiring
The sounder and beacon have separate wiring terminals. Each terminal is
duplicated to enable simple 'daisy-chain' connection of multiple units.
Line
Sounder Positive Supply (10 to 60V DC)
Sounder Negative Supply (0V)
2nd Stage Alarm Control (Connect to 0V to activate)
3rd Stage Alarm Control (Connect to 0V to activate)
Beacon Positive Supply (10 to 60V DC)
Beacon Negative Supply (0V)
Controls
a. Tone Selection
The first and second stage alarm tones are independently set using
6-way dipswitches S1 and S2 respectively. The required settings are
shown in the table overleaf. The third stage alarm tone is pre-set to
complement the selected first stage tone as shown in the table.
b. Volume Control
The sound output of the unit can be reduced by up to 20dBA by
adjusting the potentiometer.
c. Beacon Flash Controls (If fitted)
The flash mode of the beacon can be altered using the 2-way
dipswitch marked
Nexus 110 DC Sounder & Sounder-Beacon
Installation Instructions
1st Unit
Switch
1
2
Technical Specification:
Supply Voltage Range
Current – Sounder
Current –Beacon
(Where fitted)
Peak Sound Level
Number of Tones
Volume Control
Terminal Marking
+
Remote Tone Switching
-
S2
Operating Temperature
S3
+
Casing
-
IP Rating
Synchronisation
*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17V DC only.
XENON BEACON
Off
On
60 flashes per min 30 flashes per min Single Flash Double Flash
Single Flash
Double Flash
10-60V DC
10-50mA* (Typ. 45mA @ 24V, Tone 1)
Xenon - 250mA Average, 700mA Peak*,
LED - 18mA (Flashing) or 65mA (Static)*
104-116 dBA at 1m*
(Typ. 110dBA @ 24V, Tone 1)
64
20dBA typical
Provision for 3 alarm stages
(Negative voltage activation)
- 25°C to +70°C
High Impact Polycarbonate/ABS
IP66
Automatic with Klaxon Nexus and
Sonos Sounders
The European directive "Waste Electrical and Electronic Equipment" (WEEE)
aims to minimise the impact of electrical and electronic equipment waste on
the environment and human health. To conform with this directive, electrical
equipment marked with this symbol must not be disposed of in European public
disposal systems. European users of electrical equipment must now return
end-of-life equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.
To Next Unit
2nd Unit
LED BEACON
Off
On
Flashing
Static