Dimensions
• Standard box suitable for din rail 90x52X57 mm.
• Front panel 49X42 mm.
• Weight 0,2 Kg.
Power Supply
• Power supply (220÷240) Volt AC ± 10% 50/60 Hz, absorption 4 VA.
Inputs
• Two distinguished input channels for PTC sensors with possibility to connect max
six sensors in serial connections on every branch (max 1.5 K ohm per branch).
Outputs
• Output by relays with free contacts connected as per schema at the end of the
manual.
Characteristics
• Self-extinguishable NORYL Box.
• Protection degree front panel in polycarbonate: IP30
• Protection degree on terminal board side: IP20
• Two 250V AC, 5A maximum relays contact (resistive load).
• Dielectric strength between relays contacts and alimentation line 2,5KV for 60".
• Working temperature of device from -40°C to 60°C.
• Max allowed dampness in the room 90% not condensing.
• Electrical connections with fast polarised connectors.
• Technical manual in five languages (and more on request).
• Construction in accordance with rules
• Tropicalization (optional).
Place the thermocontroller on ther DIN rail.
TECHNICAL FEATURES
.
ASSEMBLY
- 7 -
ENGLISH