OWNER'S MANUAL
HT-VCL-P Condensate Pump Series
for High Temperature/Plenum Applications
The HT-VCL-P pump is designed to pump high temperature water up to 212 °F (100 °C) and/or use in ple-
num applications. Pump is also compliant with UL standard UL2043, "Fire Test for Heat and Visible Smoke
Release for Discrete Products and Their Accessories Installed in Air-handling Spaces."
This pump automatically removes condensate from an air conditioner
evaporator coil, refrigeration equipment coil, condensing furnace,
dehumidifiers, condensing boiler, or steam-generated humidifier. It is
not designed for use with steam condensate boilers over 212 °F
(100 °C). A float switch mechanism automatically starts and stops the
pump.
In the event of an overflow condition, the pump contains an overflow
detection switch, configured to open a thermostat circuit. Alterna-
tively, this switch can be reconfigured to close a circuit to operate an
external alarm or relay (purchased separately).
This product is covered by a Limited Warranty for a period of 24 months from the date of original purchase
by the consumer. For complete warranty information, refer to www.LittleGiant.com.
Specifications
Model
HT-VLC-30-P
HT-VLC-60-P
SAFETY INSTRUCTIONS
Before Getting Started
This equipment should be installed and serviced by technically qualified personnel who are familiar with
the correct selection and use of appropriate tools, equipment, and procedures. Failure to comply with
national and local electrical and plumbing codes and within Little Giant recommendations may result in
electrical shock or fire hazard, unsatisfactory performance, or equipment failure.
Know the product's application, limitations, and potential hazards. Read and follow instructions carefully to
avoid injury and property damage. Do not disassemble or repair unit unless described in this manual.
Failure to follow installation or operation procedures and all applicable codes may result in the following
hazards:
Risk of death, personal injury, or property damage due to explosion,
fire, or electric shock.
•
Do not use to pump flammable or explosive fluids such as gasoline, fuel oil, kerosene, etc.
•
Do not use in explosive atmospheres or hazardous locations as classified by the NEC, ANSI/NFPA70.
•
Do not handle a pump or pump motor with wet hands or when standing on a wet or damp surface, or in water.
•
When a pump is in its application, do not touch the motor, pipes, or water until the unit is unplugged or electrically disconnected.
•
If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power.
•
If the disconnect panel is not accessible, contact the electric company to stop service.
Volts
HZ
115
60
208-230
50/60
277
60
115
60
208-230
50/60
380-460
50/60
Amps
Watts
1.4
134
0.7
90
0.6
81
3.5
292
1.8
300
1.0
300
EN
English
Shut Off
32' (9.7 m)
32' (9.7 m)
32' (9.7 m)
62' (18.9 m)
62' (18.9 m)
62' (18.9 m)