APPENDIX A
Circuit
breaker
NEMA
Encl.
/ HMCP
size
size
Mfr.
model
0
1
A
EG
2
Eaton
3
B
4
C
JG
Catalog number
Cover screw thread
EICA ATEX
M10 x 1.5
EICB ATEX
M12 x 1.75
EICC ATEX
M12 x 1.75
Table A2 – cover bolts
Circuit breaker /
Enclosure size
HMCP
Eaton EG
A
Eaton HMCPE
Eaton EG
B
Eaton HMCPE
Eaton JG
C
Eaton HMCPJ
NOTE: Recommended distance for initial setup. Check operator for functionality. Fork
plate should be 1/8"-3/16" above circuit breaker/HMCP face.
*See Figure 4 on page 2 for further fork plate information.
Table A4 – fork plate information
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not
guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Circuit
Max.
breaker /
Torque
amps
HMCP wire
range
(based on
in.-lb.
range AWG
40°C
2
(mm
)
(N-m)
ambient)
15
50
14-3/0 (2.5-95)
See Note 1
70
125
4-350 (25-185)
180 (20)
200
NOTE 1:
14-10: 35 (4)
8: 40 (4.5)
6-4: 45 (5.1)
3-4/0: 50 (5.6)
Cover bolt torque
ft.-lb. (N-m)
35-40 (48-54)
40-45 (55-61)
40-45 (55-61)
Fork plate
distance B in
Fork plate*
inches (mm)
Type 1
3.13 (79)
Type 1
5.19 (132)
Type 2
4.75 (121)
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, NY 13208 • U.S.A.
Copyright© 2018
Starter
line wire
Starter
range
load wire
range AWG
Starter
AWG
2
2
model
(mm
)
(mm
)
18-6 (1-10)
12-6 (4-10)
AN13
12-2 (4-25)
6-1 (16-35)
8-3/0 (10-70)
8-4/0 (10-95)
Table A1 – configuration list
Starter
Eaton AN13 NEMA size 0-1
Eaton AN13 NEMA size 2
Eaton AN13 NEMA size 3
Eaton AN13 NEMA size 4
Enclosure
size
Starter
A
Eaton AN13 NEMA size 0-2
B
Eaton AN13 NEMA size 3
C
Eaton AN13 NEMA size 4
Contact plate setup
Small
Medium
Large
NOTE: Recommended distance for initial setup. Check operator for functionality. Contact
plate should be 1/16"-1/8" above starter reset button.
Based on enclosure wire
spacing
Starter
Starter
Max. wire size
torque
torque
breaker to
range
range
starter per
in.-lb.
in.-lb.
NEC wire bend
(N-m)
(N-m)
AWG (mm
26.6 (3)
See Note 2
6 (10)
29.2 (3.3)
124 (14)
25-30 (2.8-3.4) 3 (25)
200 (23)
124 (14)
1/0 (50)
NOTE 2:
12-10: 20-25 (2.3-2.8)
8-6: 25-30 (2.8-3.4)
Screw
#8-32 x 1/2" long
#8-32 x 1/2" long
#10-32 x 5/8" long
#8-32 x 3/8" long
#10-32 x 5/8" long
Table A3 – starter screws
Contact plate
Small
Medium
Large
Outside diameter in
inches (mm)
Inside thread / hole
2.50 (63)
5/16-24 thread
4.50 (114)
5/16-24 thread
5.50 (140)
5/16-24 thread
Table A5 – contact plates
Max. wire
size to enclo-
sure per NEC
wire bend
2
2
)
AWG (mm
)
3 (25)
1/0 (50)
4/0 (95)
Quantity
2
4
4
2
6
Contact
plate
distance R
in inches
(mm)
1.75 (44)
2.25 (57)
2.00 (51)
IF 1852
Revision 1
New 10/18