Code Description
Flowmeter sensitivity fac-
B28
tor
B29 Restoring Factory Values Set the value to 10
Notes:
1. Parameters with more than one description vary their function and/or range in relation to the
setting of the parameter given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given
in brackets is modified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
To return to the service menu, touch the arrow at the top left of the screen.
Menu [Transparent parameters P]
By selecting a parameter on the screen, the possible values will be shown. If the values
A
shown do not match those indicated in the corresponding "Range" column, check that the
parameter B01 is correctly set to RRT.
Code Description
Heating ramp
P30
Virtual setpoint min.
P31
temperature
Heating standby time
P32
Heating Post-Circula-
P33
tion
Pump operation
P34
Modulating pump min.
P35
speed
Modulating pump start
P36
speed
Modulating pump
P37
max. speed
Pump deactivation
temperature during
P38
Post-Circulation
Pump activation hys-
teresis temperature
P39
during Post-Circula-
tion
Heating user max. set-
P40
point
Max. output in heating 0 ÷ 100%
P41
Burner shutdown in
P42
DHW
Comfort mode activa-
P43
tion temperature
Comfort mode deacti-
P44
vation hysteresis
DHW standby time
P45
192
Range
0 ÷ 60 (0 = disabled)
Range
1 ÷ 20°C/minute
0= Deactivated
1 ÷ 80°C
0 ÷ 10 minutes
0 ÷ 255 minutes
Fixed flow rate on call
Fixed continuous flow rate
Adaptive flow rate on call
Adaptive continuous flow rate
30 ÷ 100%
90 ÷ 100%
90 ÷ 100%
0 ÷ 100°C
0 ÷ 100°C
20 ÷ 90°C
Fixed
Linked to setpoint
Solar
0 ÷ 80°C
0 ÷ 20°C
30 ÷ 255 seconds
cod. 3541V280 - Rev. 00 - 03/2021
RAGGIO C
Default
20
-
Default
4°C/minute
0
4
15
Adaptive flow rate on call
30%
90%
100%
55°C
25°C
80°C
80%
Fixed
40°C
20°C
120