dirt in the gas, use a gas filter. Always blow through the gas pipe in compliance with the regulations
prior to operating the appliance. If the appliance needs to be converted to a different type of gas
than that indicated on the type plate, the supplier of the appliance must be contacted. The supplier
can advise you which parts must be replaced in order to ensure correct operation of the appliance
with the desired type of gas. Conversion to a different type of gas is not permitted in Belgium.

2.4 Electrical connection

Installation must comply with the relevant local and/or national regulations. Ensure that there is a
correct connection group with a mains fuse. The electrical diagram is displayed on the appliance. A
basic diagram for the GS+ appliance can be found in chapter 8 and 9 Electrical diagrams. In the case
of the G+ with a centrifugal fan, please refer to the diagram on the appliance.
PLEASE NOTE:
– The appliance must be adequately earthed. The appliance must be fitted with an isolator switch
which interrupts phase and zero (not earth).
– The isolator switch must be accessible at all times.
– Never, under any circumstances, allow the supply to the appliance to be interrupted by other
switches. This could result in the appliance overheating.
– The unit is phase sensitive.
2.5 Siphon [1]
The boiler siphon that is included in the scope of supply must be connected to the appliance.
The boiler siphon must connect to the odour trap siphon in the drainage system to the sewer via
an open connection. Make sure that the siphon is protected against frost (risk of freezing).
3.0 Controls
3.1 Room thermostat and reset button
The room thermostat must be located at a height of approx. 1.5m and not directly within the flow
of warm air. Connect the room thermostat using a shielded data cable in accordance with the wiring
diagram supplied for the appliance. Refer also to the technical information handbook supplied with
the room thermostat. Incorrect connection will render the manufacturer's warranty void.
PLEASE NOTE:
– The maximum lengths and diameters are specified in the table [26].
– Earth the cable shielding to the appliance.
– For connecting multiple appliances, see [25] + [26]
3.2 Choice of bus cable
Selection of the correct type of bus cable is based on the specific model for the country concerned.
When selecting the cable, the values noted in the technical details must be complied with. Bus cables
of the appropriate specifications, which are offered in countries with an EIB market, are:
YCYM
EIB specification
J-Y(st)Y
EIB specification
JH(st)H
10
Fixed system
Dry, damp, wet rooms
In the open air (no direct exposure to sunlight)
Face-fit, flush-fit, in conduits
Fixed system
Only in interior spaces
Face-fit, in conduits
Halogen-free conduits, remote system