Mains and charging current risks
Make sure the cables are always connected to the correct terminal. An electrical shock can be lethal. In general, any
electric shock can be d angerous to your health.
CE labeling
The product is CE compliant.

Connecting and Grounding

Connect wires in indicated order 1 2 3 4 5 6 7 to avoid any installation faults
To avoid any damaging voltage on the wires, first connect the wire t o the controller, then to the battery, p anel or
to the load
Minimum recommended wire size: 10 mm ²
Make sure the wire length between battery and controller is as short as possible
Be aware that all negative wires of CIS-N-MPPT 100/ 30 are connected together and therefore have the same
electrical potential. If any grounding is required further to the casing , alw ays d o th is on the negative wires.
Grounding of the casing is done b y the grounding post on the left side.
The controller w arms up during operation, and should therefore be installed on a non flammable surface only.
When connecting inductive loads (mot ors, relays, etc.) a freewheel diode must b e connected in parallel t o the
loads in the reverse biased direction.
Inverters should always b e connected directly to the b attery due to their high inrush currents.
Function
Negative battery terminal
Positive b attery terminal
Negative panel terminal
Positive p anel terminal
Negative load terminal
Positive load terminal
Dimming signal terminal
www.phocos.com
Wire size (cross section)
Cable m arker
COMMON -
BATTERY +
COMMON -
SOLAR +
COMMON -
LOAD +
---
3.3 mm
2
3.3 mm
2
3.3 mm
2
3.3 mm
2
3.3 mm
2
3.3 mm
2
0.25 mm
2
1 2 |
Color
Black
Red
Black
Yellow
Black
Orange
Black
P a g e